A953 HANDY GOT
Connection to PLC by Yaskawa Electric 9
9-4
c) When the CP-9300MS is used
d) When the PROGIC-8 is used (when the 15-pin D-Sub port is used)
2) Used connectors and connector covers
-
Connector on the side of the cable dedicated to the GOT
The connector of the cable dedicated to the GOT (F9GT-HCAB-
M) has the following
model name. Use a counterpart connector compatible with this connector.
17JE-23250-02 (D8A2)
25-pin D-Sub, male connector manufactured by DDK Ltd. (DDK)
The cable dedicated to the GOT (F9GT-HCAB1-
M) is the untied wire type.
-
Port on the side of the PLC by Yaskawa Electric
Use a connector compatible with the PLC by Yaskawa Electric.
GOT side
(F9GT-HCAB
-3M)
(
= none or 1)
Cable connection and signal direction
Yaskawa Electric PLC
side
(9-pin D-Sub, male,
milli-thread type)
Signal
name
Untied
wire
color
Pin
number
Pin
number
Signal
name
CN2
CN3
CD(DCD)
Blue
8
1
FG
Not used
RD(RXD)
Red
4
2
TXD
SD(TXD)
Black
2
3
RXD
ER(DTR) White
3
4
RTS
SG(GND) Orange
10
5
OP
CTS
DR(DSR) Green
5
6
DSR Not used
RS(RTS) Yellow
6
7
GND
CS(CTS) Brown
7
8
PWR Not used
FG
(SHIELD)
Drain
wire
1
9
DTR Not used
GOT side
(F9GT-HCAB
-3M)
(
= none or 1)
Cable connection and signal direction
Yaskawa Electric PLC
side
(15-pin D-Sub, male,
milli-thread type)
Signal
name
Untied
wire
color
Pin
number
Pin
number
Signal
name
CD(DCD)
Blue
1
1
FG
RD(RXD)
Red
4
2
TXD
SD(TXD)
Black
2
3
RXD
ER(DTR) White
3
4
RTS
SG(GND) Orange
10
5
CTS
DR(DSR) Green
5
6
DSR
RS(RTS) Yellow
6
7
GND
CS(CTS) Brown
7
8
NC
FG
(SHIELD)
Drain
wire
1
9
DTR
Class D grounding
Class D grounding
Summary of Contents for A953GOT-LBD-M3-H
Page 4: ...A953 HANDY GOT ii ...
Page 6: ...A953 HANDY GOT iv ...
Page 14: ...A953 HANDY GOT xii MEMO ...
Page 28: ...A953 HANDY GOT Introduction 1 1 8 MEMO ...
Page 42: ...A953 HANDY GOT Installation Wiring 2 2 14 MEMO ...
Page 58: ...A953 HANDY GOT Wiring and Handling of Switches 3 3 16 MEMO ...
Page 72: ...A953 HANDY GOT Specifications 4 4 14 MEMO ...
Page 80: ...A953 HANDY GOT CPU Direct Connection 6 6 6 MEMO ...
Page 98: ...A953 HANDY GOT Connection to PLC by Omron 8 8 10 MEMO ...
Page 104: ...A953 HANDY GOT Connection to PLC by Yaskawa Electric 9 9 6 MEMO ...
Page 108: ...A953 HANDY GOT Connection to PLC by Allen Bradley 10 10 4 MEMO ...
Page 130: ...A953 HANDY GOT Connection to PLC by Siemens 13 13 4 MEMO ...
Page 134: ...A953 HANDY GOT Diagnostics 14 14 4 MEMO ...
Page 141: ......