A953 HANDY GOT
CPU Direct Connection 6
6-4
b) When the port of the connected FX
1N
-232-BD, FX
2N
-232-BD or FX
2NC
-232ADP is the 9-pin
D-Sub type
c) When the port of the connected FX
0N
-232ADP is the 25-pin D-Sub type
GOT side (F9GT-HCAB
-3M)
(
= none or 1)
Cable connection and signal direction
FXCPU side (9-
pin D-Sub, male,
#4-40UNC inch-
thread type)
Signal
name
Untied
wire color
Pin
number
Pin
number
Signal
name
CD(DCD)
Blue
8
1
CD(DCD)
RD(RXD)
Red
4
2
RD(RXD)
SD(TXD)
Black
2
3
SD(TXD)
ER(DTR)
White
3
4
ER(DTR)
SG(GND)
Orange
10
5
SG(GND)
DR(DSR)
Green
5
6
DR(DSR)
RS(RTS)
Yellow
6
7
RS(RTS)
CS(CTS)
Brown
7
9
CS(CTS)
FG
(SHIELD)
Drain wire
1
−
FRAME
GOT side (F9GT-HCAB
-3M)
(
= none or 1)
Cable connection and signal direction
FXCPU side (25-
pin D-Sub, male,
milli-thread type)
Signal
name
Untied
wire color
Pin
number
Pin
number
Signal
name
CD(DCD)
Blue
8
8
CD(DCD)
RD(RXD)
Red
4
3
RD(RXD)
SD(TXD)
Black
2
2
SD(TXD)
ER(DTR)
White
3
20
ER(DTR)
SG(GND)
Orange
10
7
SG(GND)
DR(DSR)
Green
5
6
DR(DSR)
RS(RTS)
Yellow
6
4
RS(RTS)
CS(CTS)
Brown
7
5
CS(CTS)
FG
(SHIELD)
Drain wire
1
−
FRAME
SHIELD
Class D grounding
SHIELD
Class D grounding
Summary of Contents for A953GOT-LBD-M3-H
Page 4: ...A953 HANDY GOT ii ...
Page 6: ...A953 HANDY GOT iv ...
Page 14: ...A953 HANDY GOT xii MEMO ...
Page 28: ...A953 HANDY GOT Introduction 1 1 8 MEMO ...
Page 42: ...A953 HANDY GOT Installation Wiring 2 2 14 MEMO ...
Page 58: ...A953 HANDY GOT Wiring and Handling of Switches 3 3 16 MEMO ...
Page 72: ...A953 HANDY GOT Specifications 4 4 14 MEMO ...
Page 80: ...A953 HANDY GOT CPU Direct Connection 6 6 6 MEMO ...
Page 98: ...A953 HANDY GOT Connection to PLC by Omron 8 8 10 MEMO ...
Page 104: ...A953 HANDY GOT Connection to PLC by Yaskawa Electric 9 9 6 MEMO ...
Page 108: ...A953 HANDY GOT Connection to PLC by Allen Bradley 10 10 4 MEMO ...
Page 130: ...A953 HANDY GOT Connection to PLC by Siemens 13 13 4 MEMO ...
Page 134: ...A953 HANDY GOT Diagnostics 14 14 4 MEMO ...
Page 141: ......