A953 HANDY GOT
Connection to PLC by Yaskawa Electric 9
9-2
9.2
Initial setting
1) Setting in the PLC by Yaskawa Electric
When connecting the GOT to the PLC by Yaskawa Electric, set the communication and the
port shown below using a peripheral tool.
For the details of the setting method, refer to the INSTRUCTION MANUAL of the PLC by
Yaskawa Electric.
*1 The allowable upper limit varies depending on the connected PLC by Yaskawa Electric.
2) Setting in the GOT
When connecting the GOT to the PLC by Yaskawa Electric, the transmission speed should
be set in the GOT in accordance with the setting in the used PLC by Yaskawa Electric.
Set the transmission speed using the utility function of the GOT.
For the details of the utility function, refer to the GOT-A900 SERIES OPERATING MANUAL
(EXTENSION FUNCTION/OPTIONAL FUNCTION FOR SW
D5C-GOTR-PACKE).
Point
After the system program (such as the basic OS and the communication driver) is installed in
the GOT, then the power of the GOT is turned off once and turned on again, the utility function
can be started up.
After starting up the GOT, touch the "Setup" icon to display the "Setup" screen, then perform
the settings related to connection of the PLC by Yaskawa Electric.
Item
Set value
Address
1
Protocol
MEMOBUS
Mode
RTU
Data length
8 bits
Parity
EVEN
Stop bit
1 bit
Communication speed (transmission speed)
*1
4800bps/9600bps/19200bps/38400bps
Setting item
Description
Factory setting
Baud rate
Choose the transmission speed (4800, 9600, 19200, 38400).
19200
START UP TIME
Set how many seconds after GOT power-on the communication
with the PLC CPU will be started.
1
SEND MESSAGE DELAY
Set the waiting time from when the GOT has received data from
the PLC CPU until it sends next data to the PLC CPU.
0
Summary of Contents for A953GOT-LBD-M3-H
Page 4: ...A953 HANDY GOT ii ...
Page 6: ...A953 HANDY GOT iv ...
Page 14: ...A953 HANDY GOT xii MEMO ...
Page 28: ...A953 HANDY GOT Introduction 1 1 8 MEMO ...
Page 42: ...A953 HANDY GOT Installation Wiring 2 2 14 MEMO ...
Page 58: ...A953 HANDY GOT Wiring and Handling of Switches 3 3 16 MEMO ...
Page 72: ...A953 HANDY GOT Specifications 4 4 14 MEMO ...
Page 80: ...A953 HANDY GOT CPU Direct Connection 6 6 6 MEMO ...
Page 98: ...A953 HANDY GOT Connection to PLC by Omron 8 8 10 MEMO ...
Page 104: ...A953 HANDY GOT Connection to PLC by Yaskawa Electric 9 9 6 MEMO ...
Page 108: ...A953 HANDY GOT Connection to PLC by Allen Bradley 10 10 4 MEMO ...
Page 130: ...A953 HANDY GOT Connection to PLC by Siemens 13 13 4 MEMO ...
Page 134: ...A953 HANDY GOT Diagnostics 14 14 4 MEMO ...
Page 141: ......