4 - 2
4 POSITIONING DEDICATED SIGNALS
The positioning dedicated devices are shown below.
It indicates the device refresh cycle of the Motion CPU for status signal with the
positioning control, and the device fetch cycle of the Motion CPU for command signal
with the positioning control.
The operation cycle and main cycle of the Motion CPU are shown below.
(a) Operation cycle
Item Q173DSCPU
Q172DSCPU
Q173DCPU(-S1)
Q172DCPU(-S1)
Number of control axes
Up to 32 axes
Up to 16 axes
Up to 32 axes
Up to 8 axes
Operation cycle
(Default)
SV22
0.44ms/ 1 to 6 axes
0.88ms/ 7 to 16 axes
1.77ms/ 17 to 32 axes
0.44ms/ 1 to 6 axes
0.88ms/ 7 to 16 axes
0.44ms/ 1 to 4 axes
0.88ms/ 5 to 12 axes
1.77ms/ 13 to 28 axes
3.55ms/ 29 to 32 axes
0.44ms/ 1 to 4 axes
0.88ms/ 5 to 8 axes
(b) Main cycle is not fixed-cycle as operation cycle. The cycle is dozens[ms] to
hundreds[ms].
REMARK
(1) In the positioning dedicated signals, "n" in "M3200+20n", etc. indicates a value
corresponding to axis No. such as the following tables.
Axis No.
n
Axis No.
n
Axis No.
n
Axis No.
n
1 0 9 8 17
16 25 24
2 1 10 9 18 17 26 25
3 2 11 10 19 18 27 26
4 3 12 11 20 19 28 27
5 4 13 12 21 20 29 28
6 5 14 13 22 21 30 29
7 6 15 14 23 22 31 30
8 7 16 15 24 23 32 31
• Calculate as follows for the device No. corresponding to each axis.
(Example) For axis 32
M3200+20n (Stop command)=M3200+20 31=M3820
M3215+20n (Servo OFF command)=M3215+20 31=M3835
• The following range is valid.
• Q172DSCPU
: Axis No.1 to 16 (n=0 to 16)
• Q172DCPU(-S1) : Axis No.1 to 8 (n=0 to 7)
(2) In the positioning dedicated signals, "n" in "M4640+4n", etc. of the "Synchronous
encoder axis status", "Synchronous encoder axis command signal" and
"Synchronous encoder axis monitor device" indicates a value corresponding to
synchronous encoder No. such as the following tables.
Synchronous encoder No.
n
Synchronous encoder No.
n
Synchronous encoder No.
n
P1 0 P5 4 P9 8
P2 1 P6 5 P10 9
P3 2 P7 6 P11 10
P4 3 P8 7 P12 11
• Calculate as follows for the device No. corresponding to each synchronous encoder.
(Example) For synchronous encoder No.12
M4640+4n (Error detection)= M4640+4 11=M4684
D1122+10n (Minor error code)= D1122+10 11= D1232
• The range (n=0 to 7) of synchronous encoder No. P1 to P8 is valid in the Q172DCPU(-S1).
Summary of Contents for Q Series
Page 1: ......
Page 19: ...A 18 MEMO ...
Page 129: ...4 90 4 POSITIONING DEDICATED SIGNALS MEMO ...
Page 134: ...5 5 5 MECHANICAL SYSTEM PROGRAM MEMO ...
Page 139: ...5 10 5 MECHANICAL SYSTEM PROGRAM MEMO ...
Page 163: ...6 24 6 DRIVE MODULE MEMO ...
Page 201: ...7 38 7 TRANSMISSION MODULE MEMO ...
Page 257: ...9 12 9 REAL MODE VIRTUAL MODE SWITCHING AND STOP RE START MEMO ...
Page 267: ...10 10 10 AUXILIARY AND APPLIED FUNCTIONS MEMO ...
Page 352: ......