![Mitsubishi Electric MELIPC MI5000 Series User Manual Download Page 31](http://html.mh-extra.com/html/mitsubishi-electric/melipc-mi5000-series/melipc-mi5000-series_user-manual_239727031.webp)
2 CLOCK FUNCTION
2.4 Clock Data Synchronization Setting Function
29
2
2.4
Clock Data Synchronization Setting Function
This function synchronizes the clock managed by the Windows part and the clock managed by the VxWorks part.
Precautions
If the clock data synchronization setting is used, data is overwritten by the clock data of the synchronization origin even if the
clock data of the synchronization destination is changed. When the time synchronization setting is used, always manipulate
the clock of the synchronization origin.
Synchronization setting
The synchronization of clock data is configured by "Clock data synchronization setting" of "Time Setting".
Window
[Basic Parameter]
[Operation Related Setting]
[Time Setting]
[Clock data synchronization setting]
Displayed items
■
When the synchronization setting is not used
The clock managed by the Windows part and the clock managed by the VxWorks part run independently. Therefore, if one
clock is changed, the other clock is not synchronized. If necessary, configure the clock data of both clocks managed by the
Windows part and VxWorks part.
Synchronization timing
When "Use" was configured for "Clock data synchronization", clock data is synchronized at the following times.
• Synchronization cycle
• When the power supply of this product is turned ON
• When the clock managed by the VxWorks part is changed
*1
*1 Synchronization occurs with a change by any of the following operations.
⋅
Time is configured by MI Configurator
⋅
Time is configured from the SNTP server
⋅
Time is configured by the C Controller module dedicated function (CCPU_SetRTC).
Item
Description
Setting range
Clock data synchronization
Configure whether to use the clock date synchronization setting.
• Use
• Do not use
(Default: Use)
Synchronization origin
Specify the clock data to be the basis of synchronization.
VxWorks part
Synchronization cycle
Specify the cycle interval to synchronize the clock data.
1 to 1440 minutes
(Default: 60 minutes)
Summary of Contents for MELIPC MI5000 Series
Page 1: ...MELIPC MI5000 Series User s Manual Application MI5122 VW ...
Page 2: ......
Page 18: ...16 MEMO ...
Page 22: ...20 1 DIAGNOSTIC AND MAINTENANCE FUNCTIONS 1 1 Watchdog Timer WDT Function MEMO ...
Page 42: ...40 5 iQSS FUNCTION MEMO ...
Page 146: ...144 11 SECURITY FUNCTION 11 3 IP Filter Function MEMO ...
Page 148: ...146 12 MELSOFT PRODUCT AND GOT CONNECTION FUNCTION 12 1 Connection Method MEMO ...
Page 150: ...148 13 SYSTEM COUNT FUNCTION MEMO ...
Page 152: ...150 14 TIMER EVENT FUNCTION MEMO ...
Page 160: ...158 15 OS LINKING FUNCTIONS 15 3 Inter OS Event Notification Function MEMO ...
Page 162: ...160 16 SERIAL INTERFACE SWITCHING FUNCTION MEMO ...
Page 165: ...17 BASIC PARAMETERS 17 1 Basic Parameter List 163 17 Operation related setting Window ...
Page 170: ...168 17 BASIC PARAMETERS 17 1 Basic Parameter List RAS setting Window ...
Page 174: ...172 17 BASIC PARAMETERS 17 1 Basic Parameter List External device connection settings Window ...
Page 313: ...APPX Appendix 10 List of VxWorks Components 311 A MEMO ...
Page 315: ...I 313 MEMO ...
Page 319: ......