Error code
Error name
Description
Corrective action
4001H
Common error
An unsupported request was executed.
• Check command data such as SLMP.
• Check the model selected by the
engineering tool.
4002H
Common error
An unsupported request was executed.
• Check command data such as SLMP.
• Check the model selected by the
engineering tool.
• Run again. If the same error is displayed
again, this may indicate a hardware fault.
Consult your local Mitsubishi
representative.
4003H
Common error
Command for which a global request cannot
be performed was executed.
Check command data such as SLMP.
4004H
Common error
A request was issued to the system file.
Check command data such as SLMP.
4005H
Common error
The volume of data to be handled by the
specified request is too large.
Check command data such as SLMP.
4006H
Common error
Initial communication has failed.
When using Ethernet communication, shift
the communication start timing.
4008H
Common error
The MELIPC is busy. (The buffer is not
empty.)
Execute it again after a while.
4021H
File related error
The specified drive (memory) does not exist
or there is an error.
• Check the specified drive (memory)
status.
• Back up the data of the /ROM folder, and
then initialize the memory.
4022H
File related error
The file with the specified file name or file
number does not exist.
Check the specified file name and file
number.
4023H
File related error
The file name and file number of the
specified file do not match.
Delete the file, and then create a file again.
4024H
File related error
The specified file cannot be handled.
The specified file cannot be handled.
4025H
File related error
The specified file is currently processing a
request from another engineering tool.
Forcibly execute the request. Or, execute it
again once the processing from another
engineering tool has been completed.
4027H
File related error
The specified range is larger than the file
size.
Check the specified range, and access
within the range.
4028H
File related error
The same file already exists.
Forcibly execute the request. Or, change
the file name and execute the request
again.
4029H
File related error
The specified file capacity cannot be
reserved.
• Review the specified file capacity, and
execute the request again.
• Delete unnecessary files of the /ROM
folder, and then execute again.
402AH
File related error
The specified file has an error.
Back up the data of the /ROM folder, and
then initialize the memory. Next, try writing
the file again.
402BH
File related error
The request cannot be executed in the
specified drive (memory).
• STOP MELIPC, and execute again.
• Delete unnecessary files of the /ROM
folder, and then execute again.
402CH
File related error
At present, request details cannot be run.
Execute it again after a while.
4030H
Device specification error
The specified device name cannot be
handled.
Check the specified device name.
4031H
Device specification error
• The specified device number is out of
range.
• MELIPC does not support the specified
device name.
• Check the specified device number.
• Check the specified device name.
4032H
Device specification error
A device name that has an error in the
device qualification, or that can be used in
SLMP random readout/random write (word
unit)/monitor registration/monitor command
(TS, TC, SS, SC, CS, CC) is specified.
• Check the specified device modification
method.
• Check the specified device name.
Summary of Contents for MELIPC MI5000 Series
Page 1: ...MELIPC MI5000 Series User s Manual Application MI5122 VW ...
Page 2: ......
Page 18: ...16 MEMO ...
Page 22: ...20 1 DIAGNOSTIC AND MAINTENANCE FUNCTIONS 1 1 Watchdog Timer WDT Function MEMO ...
Page 42: ...40 5 iQSS FUNCTION MEMO ...
Page 146: ...144 11 SECURITY FUNCTION 11 3 IP Filter Function MEMO ...
Page 148: ...146 12 MELSOFT PRODUCT AND GOT CONNECTION FUNCTION 12 1 Connection Method MEMO ...
Page 150: ...148 13 SYSTEM COUNT FUNCTION MEMO ...
Page 152: ...150 14 TIMER EVENT FUNCTION MEMO ...
Page 160: ...158 15 OS LINKING FUNCTIONS 15 3 Inter OS Event Notification Function MEMO ...
Page 162: ...160 16 SERIAL INTERFACE SWITCHING FUNCTION MEMO ...
Page 165: ...17 BASIC PARAMETERS 17 1 Basic Parameter List 163 17 Operation related setting Window ...
Page 170: ...168 17 BASIC PARAMETERS 17 1 Basic Parameter List RAS setting Window ...
Page 174: ...172 17 BASIC PARAMETERS 17 1 Basic Parameter List External device connection settings Window ...
Page 313: ...APPX Appendix 10 List of VxWorks Components 311 A MEMO ...
Page 315: ...I 313 MEMO ...
Page 319: ......