Appendix 8 List of Link Special Registers
SW0062
Current link scan time
The current link scan time value during cyclic transmission is stored. (Unit: ms)
A maximum margin of error of 1 ms is included in the stored value.
<Conditions>
Enabled when 'baton pass status' of own station (SB0047) is OFF. When 'baton pass status of own
station' (SB0047) is ON (error), the data immediately before is retained.
SW0064
Own station connection status
Stores own station connection status.
■
10H: Normal (Port 1 cable disconnection, Port 2 communicating)
■
11H: Disconnected (Port 1 cable disconnection, Port 2 cable disconnection)
■
12H: Disconnected (Port 1 cable disconnection, Port 2 line establishing)
SW0066
Actual link scan time (lowest 1 word)
Stores the link scan time value during cyclic transmission. (Unit:
μ
s)
SW0067
Actual link scan time (highest 1 word)
SW006A
Own station port 2 reception error
occurrence rate (maximum)
Stores the maximum value of the occurrence rate of the error frame reception of own station Port 2.
(Units: %)
If 'clear communications error count' (SB0006) is ON, then the stored occurrence rate is cleared.
SW006B
Own station port 2 reception error
occurrence rate (current)
Stores the current value of the occurrence rate of the error frame reception of own station Port 2.
(Units: %)
If 'clear communications error count' (SB0006) is ON, then the stored occurrence rate is cleared.
SW006D
Master operating station number
Stores the master station's station number.
• 0: No sub master function settings
<Conditions>
Enabled when 'baton pass status' of own station (SB0047) is OFF. When 'baton pass status of own
station' (SB0047) is ON (error), the data immediately before is retained.
SW006E
Sub master operating station number
Stores the sub master station's station number.
• 0: No sub master function settings
<Conditions>
Enabled when 'baton pass status' of own station (SB0047) is OFF. When 'baton pass status of own
station' (SB0047) is ON (error), the data immediately before is retained.
SW007C
Port 2 cable disconnection detection
count
Stores the Port 2 cable disconnection detection accumulated count. If 'clear communications error
count' (SB0006) is ON, the stored count is cleared.
If the count reaches the maximum value of 65535 (FFFFH), the count returns to 0 then continues.
SW007D
Port 2 received error detection count
Stores the Port 2 error data received accumulated count. The stored count is only error data not
transmitted to all stations. If 'clear communications error count' (SB0006) is ON, the stored count is
cleared.
If the count reaches the maximum value of 65535 (FFFFH), the count stops.
SW007E
Port 2 received data total count (lowest 1
word)
The Port 2 data received accumulated count is stored. If 'clear communications error count' (SB0006)
is ON, the stored count is cleared.
If the count reaches the maximum value of 4294967295 (FFFFFFFFH), the count stops.
SW007F
Port 2 received data total count (highest
1 word)
SW00A0
to
SW00A7
Baton pass status of each station
Stores each station baton pass status.
• 0: Baton pass normal station
• 1: Baton pass faulty station
The numbers within the following illustration indicate the station numbers. (
: fixed at 0)
• In the case of multiple stations that have gone from fault to normal, concurrent processing is carried
per device out for each link scan, therefore there may be several seconds variation in the time
required until "0: Baton pass normal station".
• When making a line connect or ring connection, token loss or reorganization may occur by
removing and inserting, or resetting the cable, and baton pass status may detect an error within 1
link scan.
<Conditions>
• Enabled when baton pass status of own station (SB0047) is OFF. When 'baton pass status of own
station' (SB0047) is ON (error), the data immediately before is retained.
• The status is not stored for the reserved stations and the station numbers after the maximum station
number.
No.
Name
Description
b15
b0
16 15 14 13 12
5
4
3
2
1
32 31 30 29 28
21 20 19 18 17
SW00A0
112 111 110 109 108
102 101 100 98 97
-
-
-
-
-
117 116 115 114 113
SW00A1
SW00A6
SW00A7
~
~
~
~
~
Summary of Contents for MELIPC MI5000 Series
Page 1: ...MELIPC MI5000 Series User s Manual Application MI5122 VW ...
Page 2: ......
Page 18: ...16 MEMO ...
Page 22: ...20 1 DIAGNOSTIC AND MAINTENANCE FUNCTIONS 1 1 Watchdog Timer WDT Function MEMO ...
Page 42: ...40 5 iQSS FUNCTION MEMO ...
Page 146: ...144 11 SECURITY FUNCTION 11 3 IP Filter Function MEMO ...
Page 148: ...146 12 MELSOFT PRODUCT AND GOT CONNECTION FUNCTION 12 1 Connection Method MEMO ...
Page 150: ...148 13 SYSTEM COUNT FUNCTION MEMO ...
Page 152: ...150 14 TIMER EVENT FUNCTION MEMO ...
Page 160: ...158 15 OS LINKING FUNCTIONS 15 3 Inter OS Event Notification Function MEMO ...
Page 162: ...160 16 SERIAL INTERFACE SWITCHING FUNCTION MEMO ...
Page 165: ...17 BASIC PARAMETERS 17 1 Basic Parameter List 163 17 Operation related setting Window ...
Page 170: ...168 17 BASIC PARAMETERS 17 1 Basic Parameter List RAS setting Window ...
Page 174: ...172 17 BASIC PARAMETERS 17 1 Basic Parameter List External device connection settings Window ...
Page 313: ...APPX Appendix 10 List of VxWorks Components 311 A MEMO ...
Page 315: ...I 313 MEMO ...
Page 319: ......