APPX
Appendix 1 Troubleshooting by Symptom
209
A
Initialization does not complete
Check the following items.
Cyclic transmission not possible
Check the following items.
Transient transmission not possible
Check the following items.
Check item
Corrective action
Are all LEDs off?
Initialize again.
If the same issue remains after initialization, this may indicate a hardware
fault. Consult your local Mitsubishi representative.
Does the MAIN RUN LED turn on, and is the dot matrix LED display updated?
Is the LED status different than that detailed in initialization?
Check item
Corrective action
Is the product or other station D LINK LED off or flashing?
• If the product D LINK LED is off or flashing, perform troubleshooting.
• If the other station D LINK LED is off or flashing, perform troubleshooting for
the corresponding module.
In the following settings, is a slave station set as a reserved station?
• [Application Parameter]
[CC-Link IE Field Network Parameter]
[Basic
Settings]
[Network Configuration Settings]
Cancel reservation specifications of slave stations.
In the following settings, are slave station RX/RY settings, or RWw/RWr
settings set?
• [Application Parameter]
[CC-Link IE Field Network Parameter]
[Basic
Settings]
[Network Configuration Settings]
Set slave station RX/RY or RWw/RWr ranges.
Do the station numbers set below, and the station set in the slave station
match?
• [Application Parameter]
[CC-Link IE Field Network Parameter]
[Basic
Settings]
[Network Configuration Settings]
Review slave station No.
Do the station type set below, and the connected slave station type match?
• [Application Parameter]
[CC-Link IE Field Network Parameter]
[Basic
Settings]
[Network Configuration Settings]
• Confirm that the connected slave station is correct.
• Review the station type set in network configuration settings.
Check item
Corrective action
Is the product or other station D LINK LED off or flashing?
• If the product D LINK LED is off or flashing, perform troubleshooting.
• If the other station D LINK LED is off or flashing, perform troubleshooting for
the corresponding module.
Is the baton pass status for target station correct?
In CC-Link IE Field diagnoses, specify the cause of the fault, and handle.
Are network numbers duplicated on the network?
Review duplicated network numbers.
Summary of Contents for MELIPC MI5000 Series
Page 1: ...MELIPC MI5000 Series User s Manual Application MI5122 VW ...
Page 2: ......
Page 18: ...16 MEMO ...
Page 22: ...20 1 DIAGNOSTIC AND MAINTENANCE FUNCTIONS 1 1 Watchdog Timer WDT Function MEMO ...
Page 42: ...40 5 iQSS FUNCTION MEMO ...
Page 146: ...144 11 SECURITY FUNCTION 11 3 IP Filter Function MEMO ...
Page 148: ...146 12 MELSOFT PRODUCT AND GOT CONNECTION FUNCTION 12 1 Connection Method MEMO ...
Page 150: ...148 13 SYSTEM COUNT FUNCTION MEMO ...
Page 152: ...150 14 TIMER EVENT FUNCTION MEMO ...
Page 160: ...158 15 OS LINKING FUNCTIONS 15 3 Inter OS Event Notification Function MEMO ...
Page 162: ...160 16 SERIAL INTERFACE SWITCHING FUNCTION MEMO ...
Page 165: ...17 BASIC PARAMETERS 17 1 Basic Parameter List 163 17 Operation related setting Window ...
Page 170: ...168 17 BASIC PARAMETERS 17 1 Basic Parameter List RAS setting Window ...
Page 174: ...172 17 BASIC PARAMETERS 17 1 Basic Parameter List External device connection settings Window ...
Page 313: ...APPX Appendix 10 List of VxWorks Components 311 A MEMO ...
Page 315: ...I 313 MEMO ...
Page 319: ......