![Mitsubishi Electric MELIPC MI5000 Series User Manual Download Page 261](http://html.mh-extra.com/html/mitsubishi-electric/melipc-mi5000-series/melipc-mi5000-series_user-manual_239727261.webp)
APPX
Appendix 6 List of Special Registers
259
A
SD81 to
SD111
Detailed information 1
Detailed information 1
Stores detailed information 1 for error code (SD0).
There are six types of information to be stored as shown in the following
figures:
• The type of detailed information 1 can be determined from SD80
"Detailed information 1 information category code". (The value of the
"Detailed information 1 information category code" stored in SD80
corresponds to (2), (4) to (6), (24) and (4100) shown below. )
■
(2): Drive number and file name
SD81: With or without specification
• b0: Drive No.
• b1: File name
SD82: Drive No.
SD83 to SD90: File name (8 characters from Unicode text string
header)
■
(4) Parameter information
SD81: With or without specification
• b0: Parameter type
• b1: Parameter storage destination
• b3: Parameter No.
• b4: Network No.
• b5: Station No.
• b6: System information
SD82(b0 to b7): Parameter type
• 1: Basic parameters
• 2: CC-Link IE Field Network Parameters
SD82(b8 to b15): Parameter storage location
• 4: User drive
SD83: Empty
SD84: Parameter No.
SD85: Network No.
SD86: Station No.
• 0 to 120 (0 for a master station)
S (at error
occurrence)
SD81 to
SD111
Detailed information 1
Detailed information 1
■
(5) System configuration information
SD81: With or without specification
• b4: CPU No.
• b5: Network No.
• b6: Station No.
SD82: Empty
SD83: Blank (If not specified, this is '0'.)
SD84(b0 to b7): Blank (If not specified, this is '0'.)
SD84(b8 to b15): CPU No. (If not specified, this is "0xFF". )
SD85: Network No. (If not specified, this is '0'.)
SD86: Station No. (If not specified, this is '0'.)
• 0 to 120 (0 for a master station)
■
(6) Frequency information
SD81: With or without specification
• b0: Number of times (set value)
SD82 to SD83: Number of times (If number of times (set value) is not
specified, this is '0'.)
• SD82: Lower word of the number of times (set value)
• SD83: Upper word of the number of times (set value)
■
(24) Failure information
The failure information is a part of system information.
■
(4100): Parameter information
SD81: With or without specification
• b0: Parameter type
• b1: Parameter storage destination
• b3: Parameter No.
• b4: Network No.
• b5: Station No.
• b6: System information
SD82(b0 to b7): Parameter type
• 2: CC-Link IE Field Network Parameters
SD82(b8 to b15): Parameter storage location
• 4: User drive
SD83: Empty
SD84: Parameter No.
SD85: Network No.
SD86: Station No.
• 0 to 120 (0 for a master station)
S (at error
occurrence)
No.
Name
Content
Details
Set by (when to
set)
Summary of Contents for MELIPC MI5000 Series
Page 1: ...MELIPC MI5000 Series User s Manual Application MI5122 VW ...
Page 2: ......
Page 18: ...16 MEMO ...
Page 22: ...20 1 DIAGNOSTIC AND MAINTENANCE FUNCTIONS 1 1 Watchdog Timer WDT Function MEMO ...
Page 42: ...40 5 iQSS FUNCTION MEMO ...
Page 146: ...144 11 SECURITY FUNCTION 11 3 IP Filter Function MEMO ...
Page 148: ...146 12 MELSOFT PRODUCT AND GOT CONNECTION FUNCTION 12 1 Connection Method MEMO ...
Page 150: ...148 13 SYSTEM COUNT FUNCTION MEMO ...
Page 152: ...150 14 TIMER EVENT FUNCTION MEMO ...
Page 160: ...158 15 OS LINKING FUNCTIONS 15 3 Inter OS Event Notification Function MEMO ...
Page 162: ...160 16 SERIAL INTERFACE SWITCHING FUNCTION MEMO ...
Page 165: ...17 BASIC PARAMETERS 17 1 Basic Parameter List 163 17 Operation related setting Window ...
Page 170: ...168 17 BASIC PARAMETERS 17 1 Basic Parameter List RAS setting Window ...
Page 174: ...172 17 BASIC PARAMETERS 17 1 Basic Parameter List External device connection settings Window ...
Page 313: ...APPX Appendix 10 List of VxWorks Components 311 A MEMO ...
Page 315: ...I 313 MEMO ...
Page 319: ......