![Mitsubishi Electric MELIPC MI5000 Series User Manual Download Page 108](http://html.mh-extra.com/html/mitsubishi-electric/melipc-mi5000-series/melipc-mi5000-series_user-manual_239727108.webp)
106
8 DIAGNOSTIC AND MAINTENANCE FUNCTIONS
8.3 Operating Status Management Function
remote RESET
This section shows the operation methods of remote RESET.
■
MI Configurator
Use a remote operation of MI Configurator.
[Online]
[Remote operation]
[MELIPC RESET]
A MELIPC RESET or WIN RESET cannot be run when a remote operation was performed by MI Configurator
that is installed on the Windows part of this product.
■
SLMP
For details on SLMP, refer to the following manual.
SLMP Reference Manual
Precautions
■
Enabling remote RESET
Before performing a remote RESET, enable remote RESET in MI Configurator.
[Basic Parameter]
[Operation Related Setting]
[Remote operation settings]
■
Considerations before executing a remote RESET
Set the operating status of this product to the STOP status.
Before a remote RESET, close or exit user applications of the Windows part and VxWorks part. If a remote RESET is
performed during operation of a user program, the user program or files may be corrupted.
■
Considerations after executing a remote RESET
Communication between external devices and this product are cut. Connect them again.
■
Remote RESET at error stop
If this product is stopped due to an error when a remote RESET is performed, this product starts in the operating status
configured by the switch.
■
System reset
A system reset can also be performed by the MELIPC RESET/WIN RESET switch. (
MELIPC MI5000 Series User's
Manual (Startup))
Summary of Contents for MELIPC MI5000 Series
Page 1: ...MELIPC MI5000 Series User s Manual Application MI5122 VW ...
Page 2: ......
Page 18: ...16 MEMO ...
Page 22: ...20 1 DIAGNOSTIC AND MAINTENANCE FUNCTIONS 1 1 Watchdog Timer WDT Function MEMO ...
Page 42: ...40 5 iQSS FUNCTION MEMO ...
Page 146: ...144 11 SECURITY FUNCTION 11 3 IP Filter Function MEMO ...
Page 148: ...146 12 MELSOFT PRODUCT AND GOT CONNECTION FUNCTION 12 1 Connection Method MEMO ...
Page 150: ...148 13 SYSTEM COUNT FUNCTION MEMO ...
Page 152: ...150 14 TIMER EVENT FUNCTION MEMO ...
Page 160: ...158 15 OS LINKING FUNCTIONS 15 3 Inter OS Event Notification Function MEMO ...
Page 162: ...160 16 SERIAL INTERFACE SWITCHING FUNCTION MEMO ...
Page 165: ...17 BASIC PARAMETERS 17 1 Basic Parameter List 163 17 Operation related setting Window ...
Page 170: ...168 17 BASIC PARAMETERS 17 1 Basic Parameter List RAS setting Window ...
Page 174: ...172 17 BASIC PARAMETERS 17 1 Basic Parameter List External device connection settings Window ...
Page 313: ...APPX Appendix 10 List of VxWorks Components 311 A MEMO ...
Page 315: ...I 313 MEMO ...
Page 319: ......