APPX
Appendix 2 List of Error Codes
241
A
■
CC-Link IE Field Network Basic error codes (C000H to CFFFH)
The following shows the codes for errors that occur on CC-Link IE Field Network Basic.
Error code
Error name
Description
Corrective action
CFC0H
Cyclic transmission error (master
station)
Unable to execute cyclic transmission
because multiple master stations exist in
the same network address.
Check the existence status of master
station in network.
CFC1H
Cyclic transmission error (master
station)
Unable to execute cyclic transmission
because the error occurred in cyclic
transmission.
• Take measures to reduce noise.
• If, after running this, the same error is
displayed again, consult your local
Mitsubishi representative.
CFC8H
Cyclic transmission error (master
station)
Unable to execute cyclic transmission
because the slave station controlled by
other master station exists.
• Check the existence status of master
station in network.
• Check the slave station where the error
occurred.
CFC9H
Cyclic transmission error (master
station)
Unable to execute cyclic transmission
because the slave station of the same IP
address exists in the same network
address.
• Check the existence status of slave
station in network.
• Check the slave station where the error
occurred.
CFD0H
Master station error
The port No. (61450) used in CC-Link IE
Field Network Basic has already been used.
Check the port No. used in the external
device configuration.
CFD1H
Master station error
Invalid value has been set in subnet mask.
Check the parameter setting.
CFE0H
Cyclic transmission error (slave
station)
The cyclic transmission was executed for
the slave station controlled by other master
station.
• Check the existence status of master
station in network.
• Check the slave station where the error
occurred.
CFE1H
Cyclic transmission error (slave
station)
The unusable number of occupied stations
has been specified from master station.
Check the number of occupied stations
setting in master station parameter
(Network Configuration Settings).
CFE8H
Cyclic transmission error (slave
station)
There is no response from slave station.
• Check the slave station disconnection
detection setting in master station
parameter (Network Configuration
Settings).
• Check the existence status of slave
station in network.
• Check the slave station which is
disconnected.
• Take measures to reduce noise.
CFE9H
Cyclic transmission error (slave
station)
The slave station of the same IP address
has existed in the same network address.
Check the slave station where the error
occurred.
CFF0H
Slave station error
The error occurred in slave station.
Check the slave station where the error
occurred.
Summary of Contents for MELIPC MI5000 Series
Page 1: ...MELIPC MI5000 Series User s Manual Application MI5122 VW ...
Page 2: ......
Page 18: ...16 MEMO ...
Page 22: ...20 1 DIAGNOSTIC AND MAINTENANCE FUNCTIONS 1 1 Watchdog Timer WDT Function MEMO ...
Page 42: ...40 5 iQSS FUNCTION MEMO ...
Page 146: ...144 11 SECURITY FUNCTION 11 3 IP Filter Function MEMO ...
Page 148: ...146 12 MELSOFT PRODUCT AND GOT CONNECTION FUNCTION 12 1 Connection Method MEMO ...
Page 150: ...148 13 SYSTEM COUNT FUNCTION MEMO ...
Page 152: ...150 14 TIMER EVENT FUNCTION MEMO ...
Page 160: ...158 15 OS LINKING FUNCTIONS 15 3 Inter OS Event Notification Function MEMO ...
Page 162: ...160 16 SERIAL INTERFACE SWITCHING FUNCTION MEMO ...
Page 165: ...17 BASIC PARAMETERS 17 1 Basic Parameter List 163 17 Operation related setting Window ...
Page 170: ...168 17 BASIC PARAMETERS 17 1 Basic Parameter List RAS setting Window ...
Page 174: ...172 17 BASIC PARAMETERS 17 1 Basic Parameter List External device connection settings Window ...
Page 313: ...APPX Appendix 10 List of VxWorks Components 311 A MEMO ...
Page 315: ...I 313 MEMO ...
Page 319: ......