UBC10.241, UBC10.241-N1
U
–
Series
24V, 10A, DC-UPS
May. 2008 / Rev. 1.1 DS-UBC10.241-EN
All parameters are specified at an input voltage of 24V, 10A output load, 25°C ambient and after a 5 minutes run-in time
unless otherwise noted. It is assumed that the input power source can deliver a sufficient output current.
www.pulspower.com Phone +49 89 9278 0 Germany
16/23
20.
S
AFETY
Output voltage
SELV
IEC/EN 60950-1
PELV
EN 60204-1, EN 50178, IEC 60364-4-41
Max. allowed voltage between any input, output or signal pin and ground:
60Vdc or 42.4Vac
Class of protection
II
PE (Protective Earth) connection is not required
Isolation resistance
> 5MOhm
Power port to housing, 500Vdc
Dielectric strength
500Vac
Power port to signal port
500Vac
Power port / signal port to housing
Touch current (leakage current)
The leakage current which is produced by the DC-UPS itself depends on the input
voltage ripple and need to be investigated in the final application.
For a smooth DC input voltage, the produced leakage current is less than 100
μ
A.
21.
A
PPROVALS
UL
508
IND. CONT. EQ.
18WM
LISTED E198865 listed for use in U.S.A. (UL 508) and
Canada (C22.2 No. 14-95)
Industrial Control Equipment
UL
60950-1
RECOGNIZED E137006 recognized for the use in
U.S.A. (UL 60950-1) and Canada (C22.2 No. 60950)
Information Technology Equipment, Level 5
UL
1604
RECOGNIZED E246877 recognized for use in U.S.A. (UL 1604) and
Canada (C22.2 No. 213-M1987)
Hazardous Location Class I Div 2 T4 Groups A,B,C,D and
Class I Zone 2 Groups IIA, IIB and IIC
The unit is suitable for use in Class I Division 2 Groups A, B, C, D locations as well as for Class I
Zone 2 Groups IIA, IIB and IIC locations. Substitution of components may impair suitability for
Class I Division 2 environment. Do not disconnect equipment unless power has been switched
off. Wiring must be in accordance with Class I, Division 2 wiring methods of the National
Electrical Code, NFPA 70, and in accordance with other local or national codes.
CSA
R
182790
C
US
CSA approval for Canada
CAN/CSA C22.2 No 107-1; CAN/ CSA 60950-1-03; UL60950-1
IEC 60950-1
IECEE
CB SCHEME
CB Scheme,
Information Technology Equipment
Marine
GL
ABS
GL (Germanischer Lloyd) classified and ABS (American Bureau for
Shipping) PDA for marine and offshore applications.
Environmental category: A, EMC2
22.
F
ULFILLED
S
TANDARDS
EN/IEC 60204-1
Safety of Electrical Equipment of Machines
EN/IEC 61131
Programmable Controllers
EN 50178, IEC 62103
Electronic Equipment in Power Installations
Summary of Contents for 4350006.71
Page 12: ...Page 12 Laser Safety thicknessCONTROL MTS 8201 LLT 4350006 71 ...
Page 62: ...Page 62 Instruction Manual Software thicknessCONTROL MTS 8201 LLT 4350006 71 ...
Page 64: ...Page 64 Pneumatic Plan thicknessCONTROL MTS 8201 LLT 4350006 71 ...
Page 70: ...Page 70 Declaration of Incorporation thicknessCONTROL MTS 8201 LLT 4350006 71 ...
Page 95: ...Operating Instructions scanCONTROL 29xx ...
Page 100: ......
Page 135: ...Page 41 Operation of the Sensor with a PC scanCONTROL 29xx Fig 24 Predefined measuring fields ...
Page 193: ......
Page 194: ......
Page 229: ......