UBC10.241, UBC10.241-N1
U
–
Series
24V, 10A, DC-UPS
May. 2008 / Rev. 1.1 DS-UBC10.241-EN
All parameters are specified at an input voltage of 24V, 10A output load, 25°C ambient and after a 5 minutes run-in time
unless otherwise noted. It is assumed that the input power source can deliver a sufficient output current.
www.pulspower.com Phone +49 89 9278 0 Germany
15/23
18.
E
NVIRONMENT
Operational temperature
0°C to +40°C (32°F to 104°F)
Full output power
Storage temperature
-20°C to +50°C (-4°F to 122°F)
Storage and transportation
Humidity
5 to 95% r.H.
IEC 60068-2-30
Do not energize while condensation is present
Vibration sinusoidal
2-17.8Hz: ±1.6mm; 17.8-500Hz: 1g *) IEC 60068-2-6
Shock
15g 6ms, 10g 11ms *)
IEC 60068-2-27
Altitude
0 to 6000m
Approvals apply only up to 2000m
Over-voltage category
III
EN 50178
II
EN 50178 above 2000m altitude
Degree of pollution
2
EN 50178, not conductive
*) Use wall mounting accessory for higher values.
Fig. 18-1
Normal Mode:
Output current vs.
ambient temperature
Fig. 18-2
Buffer Mode: Output current vs.
ambient temperature
Allowable Output
Current in Normal Mode
0
0
10
20
60°C
2.5
5
7.5
10
12.5
15A
continuous
Ambient Temperature
30
40
50
Allowable Output
Current in Buffer Mode
0
0
10
20
60°C
2.5
5
7.5
10
12.5
15A
continuous
Ambient Temperature
for typ. 5s
30
40
50
The ambient temperature is defined 2cm below the unit.
19.
P
ROTECTION
F
EATURES
Output
protection
Electronically protected against overload, no-load and short-circuits
Output over-voltage protection
in buffer mode
typ. 32Vdc
max. 35Vdc
In case of an internal defect, a redundant circuitry
limits the maximum output voltage. The output
automatically shuts-down and makes restart attempts.
Degree of protection
IP20
EN/IEC 60529
Penetration protection
> 3.5mm
E.g. screws, small parts
Reverse battery polarity protection
yes
Max. –35Vdc;
Wrong battery voltage protection
yes
Max. +35Vdc (e.g. 24V battery instead of 12V battery)
Battery deep discharge protection
yes
The limit is battery current dependent
Over temperature protection
yes
Output shut-down with automatic restart
Input
over-voltage
protection
yes
Max. 35Vdc, no harm or defect of the unit
Internal
input
fuse
25A,
blade type
No user accessible part, no service part
Summary of Contents for 4350006.71
Page 12: ...Page 12 Laser Safety thicknessCONTROL MTS 8201 LLT 4350006 71 ...
Page 62: ...Page 62 Instruction Manual Software thicknessCONTROL MTS 8201 LLT 4350006 71 ...
Page 64: ...Page 64 Pneumatic Plan thicknessCONTROL MTS 8201 LLT 4350006 71 ...
Page 70: ...Page 70 Declaration of Incorporation thicknessCONTROL MTS 8201 LLT 4350006 71 ...
Page 95: ...Operating Instructions scanCONTROL 29xx ...
Page 100: ......
Page 135: ...Page 41 Operation of the Sensor with a PC scanCONTROL 29xx Fig 24 Predefined measuring fields ...
Page 193: ......
Page 194: ......
Page 229: ......