UBC10.241, UBC10.241-N1
U
–
Series
24V, 10A, DC-UPS
May. 2008 / Rev. 1.1 DS-UBC10.241-EN
All parameters are specified at an input voltage of 24V, 10A output load, 25°C ambient and after a 5 minutes run-in time
unless otherwise noted. It is assumed that the input power source can deliver a sufficient output current.
www.pulspower.com Phone +49 89 9278 0 Germany
8/23
10.
E
FFICIENCY AND
P
OWER
L
OSSES
Efficiency
typ.
97.8%
Normal mode, 10A output current, battery fully charged
Power losses
typ.
2.9W
Normal mode, 0A output current, battery fully charged
typ.
5.5W
Normal mode, 10A output current, battery fully charged
typ.
5.0W
During battery charging, 0A output current
Fig. 10-1
Efficiency at 24V, typ.
Fig. 10-2
Losses at 24V, typ.
Efficiency vs. output
current in normal mode
94.5
3
9
95.5
96.0
97.0
15A
95.0
96.5
97.5
98%
Output Current
5
7
11
13
Power losses versus output
current in normal mode
0
0
7.5
2
3
5
15A
1
4
6
7
8W
Output Current
2.5
5
10
12.5
11.
F
UNCTIONAL
D
IAGRAM
Fig. 11-1
Functional diagram
DC-UPS Control unit with integrated battery
Battery Charger
&
Tester
Cut-off
Relay
24V
Power
Supply
Input
-
+
Reverse
Polarity
Protection
Input Fuse
&
*
(5)
(6)
Ready
Contact
(1)
(2)
Buffering
Contact
(3)
(4)
Electronic
Current
Limiter
Buffered
Load
+
-
Output
Controller
Diagnosis LED (yellow)
Check Wiring LED (red)
Status LED (green)
Buffer-time Limiter
10s, 30s, 1m, 3m, 10m,
Inhibit -
I
Replace
Battery
Contact
Step-up
Converter
(7)
(8)
12V 5Ah battery
+
-
Fuse
*)
Return current protection; This feature utilizes a Mosfet instead of a diode in order to minimize the voltage drop and power
losses.
Summary of Contents for 4350006.71
Page 12: ...Page 12 Laser Safety thicknessCONTROL MTS 8201 LLT 4350006 71 ...
Page 62: ...Page 62 Instruction Manual Software thicknessCONTROL MTS 8201 LLT 4350006 71 ...
Page 64: ...Page 64 Pneumatic Plan thicknessCONTROL MTS 8201 LLT 4350006 71 ...
Page 70: ...Page 70 Declaration of Incorporation thicknessCONTROL MTS 8201 LLT 4350006 71 ...
Page 95: ...Operating Instructions scanCONTROL 29xx ...
Page 100: ......
Page 135: ...Page 41 Operation of the Sensor with a PC scanCONTROL 29xx Fig 24 Predefined measuring fields ...
Page 193: ......
Page 194: ......
Page 229: ......