UBC10.241, UBC10.241-N1
U
–
Series
24V, 10A, DC-UPS
May. 2008 / Rev. 1.1 DS-UBC10.241-EN
All parameters are specified at an input voltage of 24V, 10A output load, 25°C ambient and after a 5 minutes run-in time
unless otherwise noted. It is assumed that the input power source can deliver a sufficient output current.
www.pulspower.com Phone +49 89 9278 0 Germany
14/23
17.
EMC
The unit is suitable for applications in industrial environment as well as in residential, commercial and light industry
environment without any restrictions. CE mark is in conformance with EMC guideline 89/336/EC and 93/68/EC and the
low-voltage directive (LVD) 73/23/EC, 93/68/EC.
A detailed EMC Report is available on request.
EMC Immunity
EN 61000-6-1, EN 61000-6-2
Generic standards
Electrostatic discharge
EN 61000-4-2
Contact discharge
Air discharge
8kV
15kV
Criterion A*)
Criterion A *)
Electromagnetic RF field
EN 61000-4-3 80MHz-1GHz
10V/m
Criterion
A
Fast transients (Burst)
EN 61000-4-4
Out- and input lines
2kV
Criterion A
Signal lines **)
2kV
Criterion A
Surge voltage
EN 61000-4-5
Æ
-
Input +
Æ
-
+ / -
Æ
housing
500V
500V
500V
Criterion A
Criterion A
Criterion A
Conducted disturbance
EN 61000-4-6
0,15-80MHz
10V
Criterion A
*) DIN-Rail
earthed
**) Tested with coupling clamp
EMC Emission
EN 61000-6-3, EN 61000-6-4
Generic standards
Conducted emission
EN 55022
Input lines
Class B *)
EN 55022
Output lines
Class B *)
Radiated emission
EN 55011, EN 55022
Class B
This device complies with FCC Part 15 rules.
Operation is subjected to the following two conditions: (1) this device may not cause harmful interference, and (2) this
device must accept any interference received, including interference that may cause undesired operation.
*)
Informative measurement with voltage probe
Switching frequencies
The DC-UPS has three converters with three different
switching frequencies included.
Switching frequency of boost converter
100kHz
Constant frequency
Switching frequency of electronic output current limitation
78kHz
Constant frequency
Switching frequency of battery charger
19.5kHz
Constant frequency
Summary of Contents for 4350006.71
Page 12: ...Page 12 Laser Safety thicknessCONTROL MTS 8201 LLT 4350006 71 ...
Page 62: ...Page 62 Instruction Manual Software thicknessCONTROL MTS 8201 LLT 4350006 71 ...
Page 64: ...Page 64 Pneumatic Plan thicknessCONTROL MTS 8201 LLT 4350006 71 ...
Page 70: ...Page 70 Declaration of Incorporation thicknessCONTROL MTS 8201 LLT 4350006 71 ...
Page 95: ...Operating Instructions scanCONTROL 29xx ...
Page 100: ......
Page 135: ...Page 41 Operation of the Sensor with a PC scanCONTROL 29xx Fig 24 Predefined measuring fields ...
Page 193: ......
Page 194: ......
Page 229: ......