IMPULSE®•G+ & VG+ Series 4 Instruction Manual - February 2017
1-7
Table 1-3: Specifications for 230 V, 460 V, and 575 V
Specification
Specification Value and Information for All Models
Certification
UL, cUL, CSA, CE, RoHS
Crane Duty Classification
Rated for CMAA Crane Duty Class A - F only (or equivalent)
Rated input power supply volts
& freq
3-phase 200 to 240 VAC 50/60 Hz for a 230 VAC-rated drive
3-phase 380 to 480 VAC 50/60 Hz for a 460 VAC-rated drive
3-phase 500 to 600 VAC 50/60 Hz for a 575 VAC-rated drive
Control Voltage
120 VAC (50/60 Hz) standard
42–48 VAC (50/60 Hz)
24 VAC (50/60 Hz)
24 VDC
Allowable input and control
voltage fluctuation
+10% or -15% of nominal
Allowable input frequency
fluctuation
±5% of nominal
Allowable control frequency
fluctuation
±3 Hz of nominal
Control method
Fully digital, V/f, open loop vector, or flux vector control; sine-wave, pulse-
width-modulated
Maximum output voltage (VAC) 3-phase 200 to 240 VDC (proportional to input voltage)
3-phase 380 to 480 VDC (proportional to input voltage)
3-phase 500 to 600 VDC (proportional to input voltage)
Rated frequency (Hz)
150 Hz standard (400 Hz optional, consult factory and equipment
manufacturer)
Output speed control range
FLV: 1500:1; OLV: 200:1; V/f: 40:1
Output frequency accuracy
0.01%—with digital reference command
0.1%—with analog reference command; 10 bits/10 V
Frequency reference resolution Digital: 0.01 Hz; analog: 0.03 Hz (at 60 Hz)
Output frequency resolution
0.01 Hz
Overload capacity
150% of drive rated load for 1 min
Remote frequency reference
sources
0–10 VDC (20k
); 4–20 mA (250
); ±10 VDC serial (RS-485)
Accel/decel times
0.1 to 6000.0 sec—4 sets; 8 parameters are independently adjustable
Braking torque
150% or more with dynamic braking
DC Link Choke
Models 2085 to 2415 and 4045 to 41090 come with a built-in DC link choke.
Internal Braking Transistor
Models 2003 to 2115, 4001 to 4060, and 5001 to 5041 come with an internal
braking transistor (B1 and B2 terminals).
Motor overload protection
UL recognized electronic thermal overload relay; field-programmable
Overcurrent protection level
(OC1)
200% of drive rated current
Circuit protection
Ground fault and blown-fuse protection
Overvoltage protection level
230 VAC class: Stops when DC bus voltage exceeds approx. 410 VDC
460 VAC class: Stops when DC bus voltage exceeds approx. 820 VDC
575 VAC class: Stops when DC bus voltage exceeds approx. 1040 VDC
Undervoltage protection level
230 VAC class: Stops when DC bus voltage falls below approx. 190 VDC
460 VAC class: Stops when DC bus voltage falls below approx. 380 VDC
575 VAC class: Stops when DC bus voltage falls below approx. 475 VDC
* 2kHz carrier frequency
** Maximum rated temperature of 65°C at the drive chassis with factory approved air handling system
Summary of Contents for Impulse G+ series 4
Page 2: ......
Page 6: ...IMPULSE G VG Series 4 Instruction Manual February 2017 iv This page intentionally left blank...
Page 12: ...IMPULSE G VG Series 4 Instruction Manual February 2017 This page intentionally left blank...
Page 13: ...C h a p t e r 1 Introduction...
Page 14: ...IMPULSE G VG Series 4 Instruction Manual February 2017 1 2 This page intentionally left blank...
Page 26: ...IMPULSE G VG Series 4 Instruction Manual February 2017 1 14 This page intentionally left blank...
Page 27: ...C h a p t e r 2 Installation...
Page 28: ...IMPULSE G VG Series 4 Instruction Manual February 2017 2 2 This page intentionally left blank...
Page 40: ...IMPULSE G VG Series 4 Instruction Manual February 2017 2 14 This page intentionally left blank...
Page 41: ...C h a p t e r 3 Wiring...
Page 42: ...IMPULSE G VG Series 4 Instruction Manual February 2017 3 2 This page intentionally left blank...
Page 66: ...IMPULSE G VG Series 4 Instruction Manual February 2017 3 26 This page intentionally left blank...
Page 67: ...C h a p t e r 4 Getting Started...
Page 68: ...IMPULSE G VG Series 4 Instruction Manual February 2017 4 2 This page intentionally left blank...
Page 87: ...C h a p t e r 5 Programming Advanced Features...
Page 88: ...IMPULSE G VG Series 4 Instruction Manual February 2017 5 2 This page intentionally left blank...
Page 223: ...C h a p t e r 6 Troubleshooting...
Page 224: ...IMPULSE G VG Series 4 Instruction Manual February 2017 6 2 This page intentionally left blank...
Page 255: ...a p p e n d i x A IMPULSE G VG Series 4 Parameter Listing...
Page 256: ...IMPULSE G VG Series 4 Instruction Manual February 2017 A 2 This page intentionally left blank...