IMPULSE®•G+ & VG+ Series 4 Instruction Manual – February 2017
5-113
Table 5-95: Torque Detection Parameter Settings - continued
Table 5-96: Torque Detection 2 Select Descriptions
Overtorque detection 2 functions the same as overtorque/undertorque detection 1 (L06-01), except
that “OT2/UT2” is displayed on the digital operator instead. This function is used when two types of
detection are output to the multi-function output terminals.
Parameter Display
Function
Range
Default
L06-02
Torq Det 1 Lvl
Sets the overtorque detection as a
percentage of inverter rated current,
during V/f control, and motor rated
torque during vector control.
0–300%
150
L06-03
Torq Det 1 Time
The overtorque detection delay time
inserts a delay, between the time
motor current (or torque) exceeds
the overtorque level (L06-02) and
when the overtorque detection
function is enabled. The digital
operator then displays “OT1”.
0.0–10.0 sec
0.1
L06-04
Torq Det 2 Sel
Activates overtorque/undertorque
detection, and selects whether
detection generates an alarm or a
fault.
0–8
0
0
Disabled
1
OT@SpdAgree-Alm
2 OT At RUN - Alm
3
OT@SpdAgree-Flt
4
OT At RUN - Flt
5
UT@SpdAgree-Alm
6
UT At RUN - Alm
7
UT@SpdAgree-Flt
8
UT At RUN - Flt
Setting
Description
0
Overtorque/undertorque detection is disabled (
factory default
).
1
Overtorque detection is enabled whenever at the speed agree level (when inverter is not
accelerating or decelerating). Continue running after detection (OT2 alarm).
2
Overtorque detection is enabled always. Continue running after detection (OT2 alarm).
3
Overtorque detection is enabled whenever at the speed agree level. Coast to a stop after
detection (OT2 fault).
4
Overtorque detection is enabled always. Coast to a stop after detection (OT2 fault).
5
Undertorque detection is enabled whenever at the speed agree level (when inverter is not
accelerating or decelerating). Continue running after detection (UT2 alarm).
6
Undertorque detection is enabled always. Continuing running after detection (UT2 alarm).
7
Undertorque detection is enabled whenever at the speed agree level. Coast to a stop after
detection (UT2 fault).
8
Undertorque detection is enabled always. Coast to stop after detection (UT2 fault)
Summary of Contents for Impulse G+ series 4
Page 2: ......
Page 6: ...IMPULSE G VG Series 4 Instruction Manual February 2017 iv This page intentionally left blank...
Page 12: ...IMPULSE G VG Series 4 Instruction Manual February 2017 This page intentionally left blank...
Page 13: ...C h a p t e r 1 Introduction...
Page 14: ...IMPULSE G VG Series 4 Instruction Manual February 2017 1 2 This page intentionally left blank...
Page 26: ...IMPULSE G VG Series 4 Instruction Manual February 2017 1 14 This page intentionally left blank...
Page 27: ...C h a p t e r 2 Installation...
Page 28: ...IMPULSE G VG Series 4 Instruction Manual February 2017 2 2 This page intentionally left blank...
Page 40: ...IMPULSE G VG Series 4 Instruction Manual February 2017 2 14 This page intentionally left blank...
Page 41: ...C h a p t e r 3 Wiring...
Page 42: ...IMPULSE G VG Series 4 Instruction Manual February 2017 3 2 This page intentionally left blank...
Page 66: ...IMPULSE G VG Series 4 Instruction Manual February 2017 3 26 This page intentionally left blank...
Page 67: ...C h a p t e r 4 Getting Started...
Page 68: ...IMPULSE G VG Series 4 Instruction Manual February 2017 4 2 This page intentionally left blank...
Page 87: ...C h a p t e r 5 Programming Advanced Features...
Page 88: ...IMPULSE G VG Series 4 Instruction Manual February 2017 5 2 This page intentionally left blank...
Page 223: ...C h a p t e r 6 Troubleshooting...
Page 224: ...IMPULSE G VG Series 4 Instruction Manual February 2017 6 2 This page intentionally left blank...
Page 255: ...a p p e n d i x A IMPULSE G VG Series 4 Parameter Listing...
Page 256: ...IMPULSE G VG Series 4 Instruction Manual February 2017 A 2 This page intentionally left blank...