IMPULSE®•G+ & VG+ Series 4 Instruction Manual – February 2017
5-92
25 During Load Flt
ON/CLOSED: When drive is in Load Float
OFF/OPEN: When drive is
not
in Load Float
26 Run Cmd is
Input
ON/CLOSED: When either a Forward or Reverse command is active on H01-xx
OFF/OPEN: When neither a Forward or Reverse command is active on H01-xx
27 Load Check Det
ON/CLOSED: When the drive has detected a Load Check fault
OFF/OPEN: Normal operation
28 Slack Cable Det
ON/CLOSED: When the drive has detected a Slack Cable
OFF/OPEN: Normal operation
29 Upper Limit
ON/CLOSED: When a UL1, UL2, or UL3 is detected
OFF/OPEN: Normal operation
2A During RUN 2
ON/CLOSED: When a run command is active and the drive is outputting voltage.
2B Upper Limit 1
ON/CLOSED: When UL1 is detected
OFF/OPEN: Normal operation
2C Upper Limit 2
ON/CLOSED: When UL2 is detected
OFF/OPEN: Normal operation
2D Lower Limit 1
ON/CLOSED: When LL1 is detected
OFF/OPEN: Normal operation
2E Lower Limit 2
ON/CLOSED: When LL2 is detected
OFF/OPEN: Normal operation
30 Lower Limit
ON/CLOSED: When LL1 or LL2 is detected
OFF/OPEN: Normal operation
31 Up/Low Limit
ON/CLOSED: UL1, UL2, UL3, LL1, or LL2 is detected
OFF/OPEN: Normal operation
32 Snap Shaft
ON/CLOSED: When the drive has detected a Snap Shaft
OFF/OPEN: Normal operation
34 Index Complete
ON/CLOSED: When the Index move is complete
OFF/OPEN: Normal operation or Index move is not complete
35 Ready for F-Ref
ON/CLOSED: When C08-04 timer has expired or the Brake Answerback is detected
H01-xx = 58 is true
OFF/OPEN: Normal operation or drive detected a BE1, BE2, BE4 alarm or is stopped.
36 Fan Alrm Det
ON/CLOSED: When the drive detects that the internal cooling fan has failed
OFF/OPEN: Normal operation
37 Maintenance
ON/CLOSED: When the Maintenance Timer U01-52
≥
C12-05
OFF/OPEN: Normal operation or the Maintenance Timer U01-52 < C12-05
38 Spd Lim @ T
Cont
ON/CLOSED: When Speed Limit has been reached while using Torque Control
OFF/OPEN: When the Speed Limit has
not
been reached when using Torque Control
39 Drive Enable
ON/CLOSED: When Drive is Enabled
OFF/OPEN: When Drive Enable (H01-xx =65) is
not
active
3B Watt-hour Pulse
ON/CLOSED: When the Watt-hour time is reached (based on setting of H02-06), the
contact will close for 200 ms
OFF/OPEN: When the Watt-hour time has
not
been reached
3D Fault or Alarm
ON/CLOSED: When either a Fault or Alarm condition is detected
OFF/OPEN: Normal operation
3E Overspeed
ON/CLOSED: When an overspeed condition is detected
OFF/OPEN: Normal operation
3F Klixon
ON/CLOSED: When a Klixon alarm is detected (H01-xx = 56 or 57 is active)
OFF/OPEN: Normal operation
Display
Function
* This output does not have an inverse output
** Contact will open when power is disconnected
Summary of Contents for Impulse G+ series 4
Page 2: ......
Page 6: ...IMPULSE G VG Series 4 Instruction Manual February 2017 iv This page intentionally left blank...
Page 12: ...IMPULSE G VG Series 4 Instruction Manual February 2017 This page intentionally left blank...
Page 13: ...C h a p t e r 1 Introduction...
Page 14: ...IMPULSE G VG Series 4 Instruction Manual February 2017 1 2 This page intentionally left blank...
Page 26: ...IMPULSE G VG Series 4 Instruction Manual February 2017 1 14 This page intentionally left blank...
Page 27: ...C h a p t e r 2 Installation...
Page 28: ...IMPULSE G VG Series 4 Instruction Manual February 2017 2 2 This page intentionally left blank...
Page 40: ...IMPULSE G VG Series 4 Instruction Manual February 2017 2 14 This page intentionally left blank...
Page 41: ...C h a p t e r 3 Wiring...
Page 42: ...IMPULSE G VG Series 4 Instruction Manual February 2017 3 2 This page intentionally left blank...
Page 66: ...IMPULSE G VG Series 4 Instruction Manual February 2017 3 26 This page intentionally left blank...
Page 67: ...C h a p t e r 4 Getting Started...
Page 68: ...IMPULSE G VG Series 4 Instruction Manual February 2017 4 2 This page intentionally left blank...
Page 87: ...C h a p t e r 5 Programming Advanced Features...
Page 88: ...IMPULSE G VG Series 4 Instruction Manual February 2017 5 2 This page intentionally left blank...
Page 223: ...C h a p t e r 6 Troubleshooting...
Page 224: ...IMPULSE G VG Series 4 Instruction Manual February 2017 6 2 This page intentionally left blank...
Page 255: ...a p p e n d i x A IMPULSE G VG Series 4 Parameter Listing...
Page 256: ...IMPULSE G VG Series 4 Instruction Manual February 2017 A 2 This page intentionally left blank...