IMPULSE®•G+ & VG+ Series 4 Instruction Manual – February 2017
5-87
A
Upper Lmt 1 N.C.
Upper Limit - Slow Down; Normally Closed. UL1 - blinking
B
Upper Lmt 2 N.C.
Upper Limit - Stop; Normally Closed. UL2 - blinking
C Lower Lmt 1 N.C.
Lower Limit - Slow Down; Normally Closed. LL1 - blinking
D Lower Lmt 2 N.C.
Lower Limit - Stop; Normally Closed. LL2 - blinking
E
M-Speed Gain 1
Micro-Speed positioning control multiplier 1. Gain is set by parameter
C02-01. (Has Priority over Micro-Speed 2)
F
Not Used
No function - Terminal is disabled.
10 M-Speed Gain 2
Micro-Speed positioning control multiplier 2. Gain is set by parameter
C02-02.
11 Load Float 1
Load Float Hold - When input during run, Load Float will remain On and
Fref is held at 0 Hz while MFDI is ON.
12 Weight Lmt N.C.
Weighted Upper Limit - UL3. Stopping Method determined by C03-08.
13 SwiftLift Enable
UltraLift Enable
Ultra/Swift Lift Enable (C06-01 = 2). Not Available for Traverse Motion.
14 Alt T-Lim Gain
Alternate Torque Limit Gain - C07-05. Use when Load Testing a Hoist.
(Internal T-Lim* C07-05)
15 Forward Jog
Forward Jog (Uses B01-17 Reference)
16 Reverse Jog
Reverse Jog (Uses B01-17 Reference)
17 Forward Inch
Forward Inch
18 Reverse Inch
Reverse Inch
19 Inch Repeat
Inch Repeat
1A Acc/Dec 2
Acceleration/Deceleration Time Changeover 2 using B05-03 and B05-04
1B Acc/Dec 3
Acceleration/Deceleration Time Changeover 3 using B05-12 and B05-13
1C Acc/Dec 4
Acceleration/Deceleration Time Changeover 4 using B05-14 and B05-15
1D Digital Chngover
Analog/Digital Reference Changeover; When B01-18 = 1 If Closed =
Digital
1F Run/Ref Src 1/2
Run/Ref Source 2 Switch - Closed = Run / Fref Selection from B03-15 /
B03-16, else B03-01/B03-02
20 through 2F
External Fault (Desired setting is possible.) Input mode: N.O. / N.C.,
Detection mode: Always / During run. See External Fault Selection (Table
5-80)
30 Program Lockout
Closed: Parameters enabled to write; Open: Parameters disabled to write
other than freq. reference (U01-01).
31 Local/Remote Sel
Local/Remote Changeover. Closed = Local
32 Ext BaseBlk N.O.
N.O.: Baseblock by ON.
33 Ext BaseBlk N.C.
N.C.: Baseblock by OFF.
34 Spd/Trq Chngover
Speed/Torque Control Changeover (ON: Torque Control)
35 Load Float 2
Zero Speed initiated. Manual Load Float Timed by C04-01.
36 Polarity Rev
Polarity Reversing command for External Torque Control. Closed =
Reverse Polarity
37 ASR Gain Switch
ON: Switches to ASR Gain 2 parameters - Forces D04-07.
38 Acc/Dec RampHold
Speed Hold 1 - Accel/decel is stopped by ON, and frequency is held.
39 OH2 Alarm Signal
External OH2 - Inverter overheat prediction (OH2 is shown by ON.)
(Alarm Only)
3A MFAI Enable
When closed, the terminals specified in H03-14 are enabled. When open,
the drive disregards the input signal to the analog terminals. The
terminals that are not set in H03-14 to be enabled by this feature will
always be enabled.
3F Fault Reset
Resets Drive Faults when ON.
41 SnapShaft Disabl
Open: Snap Shaft Detection is Enabled
Closed: Snap Shaft Detection is Disabled.
Display
Function
Summary of Contents for Impulse G+ series 4
Page 2: ......
Page 6: ...IMPULSE G VG Series 4 Instruction Manual February 2017 iv This page intentionally left blank...
Page 12: ...IMPULSE G VG Series 4 Instruction Manual February 2017 This page intentionally left blank...
Page 13: ...C h a p t e r 1 Introduction...
Page 14: ...IMPULSE G VG Series 4 Instruction Manual February 2017 1 2 This page intentionally left blank...
Page 26: ...IMPULSE G VG Series 4 Instruction Manual February 2017 1 14 This page intentionally left blank...
Page 27: ...C h a p t e r 2 Installation...
Page 28: ...IMPULSE G VG Series 4 Instruction Manual February 2017 2 2 This page intentionally left blank...
Page 40: ...IMPULSE G VG Series 4 Instruction Manual February 2017 2 14 This page intentionally left blank...
Page 41: ...C h a p t e r 3 Wiring...
Page 42: ...IMPULSE G VG Series 4 Instruction Manual February 2017 3 2 This page intentionally left blank...
Page 66: ...IMPULSE G VG Series 4 Instruction Manual February 2017 3 26 This page intentionally left blank...
Page 67: ...C h a p t e r 4 Getting Started...
Page 68: ...IMPULSE G VG Series 4 Instruction Manual February 2017 4 2 This page intentionally left blank...
Page 87: ...C h a p t e r 5 Programming Advanced Features...
Page 88: ...IMPULSE G VG Series 4 Instruction Manual February 2017 5 2 This page intentionally left blank...
Page 223: ...C h a p t e r 6 Troubleshooting...
Page 224: ...IMPULSE G VG Series 4 Instruction Manual February 2017 6 2 This page intentionally left blank...
Page 255: ...a p p e n d i x A IMPULSE G VG Series 4 Parameter Listing...
Page 256: ...IMPULSE G VG Series 4 Instruction Manual February 2017 A 2 This page intentionally left blank...