IMPULSE®•G+ & VG+ Series 4 Instruction Manual – February 2017
5-114
Table 5-97: Torque Detection Parameter Settings - continued
Table 5-98: Mechanical Fatigue Selection Description
Table 5-99: Torque Detection Parameter Settings - continued
Parameter Display
Function
Range
Default
L06-05
Torq Det 2 Lvl
Torque Detection 2 Level
0–300%
150
L06-06
Torq Det 2 Time
Torque Detection 2 Time
0.0–10.0 sec
0.1
L06-08
Mech Fatigue Sel
This function can detect an
overtorque or undertorque in a
certain speed range as a result of
machine fatigue. It is triggered by a
specified operation time and uses
the oL1 detection settings (L06-01
and L06-03).
0–8
0
0
Disabled
1
Alm Spd>L06-09
2 Alm
[Spd]>L06-09
3
Flt Spd>L06-09
4
Flt [Spd]>L06-09
5
Alm Spd<L06-09
6
Alm [Spd]<L06-09
7
Flt Spd<L06-09
8
Flt [Spd]<L06-09
Setting
Description
0
Mechanical Weakening Detection disabled (factory default).
1
Continue running (alarm only). Detected when the speed (signed) is greater than L06-09.
2
Continue running (alarm only). Detected when the speed (not signed) is greater than L06-09.
3
Interrupt drive output (fault). Detected when the speed (signed) is greater than L06-09.
4
Interrupt drive output (fault). Detected when the speed (not signed) is greater than L06-09.
5
Continue running (alarm only). Detected when the speed (signed) is less than L06-09.
6
Continue running (alarm only). Detected when the speed (not signed) is less than L06-09.
7
Interrupt drive output (fault). Detected when the speed (signed) is less than L06-09.
8
Interrupt drive output (fault). Detected when the speed (not signed) is less than L06-09.
Parameter Display
Function
Range
Default
L06-09
MechFat Det Spd
Sets the speed that triggers
Mechanical Weakening Detection.
When L06-08 is set for an unsigned
value, the absolute value is used if
the setting is negative.
-110.0–110.0%
110.0
L06-10
MechFat Det Time
Sets the time mechanical weakening
has to be detected before an alarm
or fault is triggered.
0.0–10.0 sec
0.1
L06-11
MechFat Det Hour
Sets the operation time (U01-04)
required before Mechanical
Weakening Detection is active.
0–65535
0
Summary of Contents for Impulse G+ series 4
Page 2: ......
Page 6: ...IMPULSE G VG Series 4 Instruction Manual February 2017 iv This page intentionally left blank...
Page 12: ...IMPULSE G VG Series 4 Instruction Manual February 2017 This page intentionally left blank...
Page 13: ...C h a p t e r 1 Introduction...
Page 14: ...IMPULSE G VG Series 4 Instruction Manual February 2017 1 2 This page intentionally left blank...
Page 26: ...IMPULSE G VG Series 4 Instruction Manual February 2017 1 14 This page intentionally left blank...
Page 27: ...C h a p t e r 2 Installation...
Page 28: ...IMPULSE G VG Series 4 Instruction Manual February 2017 2 2 This page intentionally left blank...
Page 40: ...IMPULSE G VG Series 4 Instruction Manual February 2017 2 14 This page intentionally left blank...
Page 41: ...C h a p t e r 3 Wiring...
Page 42: ...IMPULSE G VG Series 4 Instruction Manual February 2017 3 2 This page intentionally left blank...
Page 66: ...IMPULSE G VG Series 4 Instruction Manual February 2017 3 26 This page intentionally left blank...
Page 67: ...C h a p t e r 4 Getting Started...
Page 68: ...IMPULSE G VG Series 4 Instruction Manual February 2017 4 2 This page intentionally left blank...
Page 87: ...C h a p t e r 5 Programming Advanced Features...
Page 88: ...IMPULSE G VG Series 4 Instruction Manual February 2017 5 2 This page intentionally left blank...
Page 223: ...C h a p t e r 6 Troubleshooting...
Page 224: ...IMPULSE G VG Series 4 Instruction Manual February 2017 6 2 This page intentionally left blank...
Page 255: ...a p p e n d i x A IMPULSE G VG Series 4 Parameter Listing...
Page 256: ...IMPULSE G VG Series 4 Instruction Manual February 2017 A 2 This page intentionally left blank...