GRAFIK Eye
®
QS Control Unit Installation and Operation Guide 50
1. Verify that the shade is associated with
the intended Shade button group of the
GRAFIK Eye
®
QS control unit.
2. Tap the Shade button on the Sivoia
®
QS
Triathlon
®
shade. The Shade button LED
will turn on solid green, and the shade
will wait in this mode for 30 seconds.
3. In the GRAFIK Eye
®
QS Shade button
group associated with the shade,
simultaneously press and hold the Open
and Raise buttons for 5 seconds.
4. Use the Raise/Lower buttons to position
the shade at the desired level for the
upper limit (the maximum the shade is
allowed to open).
5. Press and hold the Open button for 5
seconds to store the current position as
the upper limit. The Open button LED will
flash quickly for 2 seconds
6. Set the lower limit: Repeat steps 2 and 3
to enter Limit Set mode.
7. Use the Raise/Lower buttons to position
the shade at the desired level for the
lower limit (the maximum the shade is
allowed to close).
8. Press and hold the Close button for
5 seconds to store the current position
as the lower limit. The Close button LED
will flash quickly for 2 seconds.
9. Repeat steps 1 through 8 to set the
upper and lower limits for each Sivoia
®
QS Triathlon
®
shade.
Tap shade button
OR
Setting Upper and Lower Limits of a Sivoia
®
QS Triathlon
®
Shade
with GRAFIK Eye
®
QS Control Unit