GRAFIK Eye
®
QS Control Unit Installation and Operation Guide 21
Scene Setup (continued)
Labeling a Scene (optional)
1. Enter programming mode.
2. Use the Master buttons to highlight
“Scene setup” and press the
“OK” button to accept.
3. Use the Master buttons to highlight
“Labels” and press the “OK” button
to accept.
4. Use the Master buttons to highlight
your desired scene. Press the
“OK” button to accept.
5. Use the Master buttons to
highlight “Custom” and press the
“OK” button to accept.
6. Use the Master buttons to scroll
through the characters (lowercase
and uppercase letters, plus numbers
0 through 9). The character you are
currently changing will be underlined
on the screen. Press OK to select
the character you want, then repeat
for all available characters. Choose
a space (no character) and press OK
for any remaining characters. Press
the “OK” button to accept.
7. The info screen will confirm that
your name has been saved.
8. Exit programming mode.
Main menu
Timeclock
Scene setup
Labels
Select scene:
Scene 1
Label scene 1
Custom
Label scene 1
1: A
A
1 / 10
OK
Master
buttons
“OK”
button
Scene setup
Levels
Labels
Saved
Enabling/Disabling Daylighting in a Scene
1. Enter programming mode.
2. Use the Master buttons to highlight “Scene
setup” and press the “OK” button to accept.
3. Use the Master buttons to highlight
“Daylighting” and press the “OK” button to
accept.
4. Use the Master buttons to highlight your desired
scene. Press the “OK” button to accept.
5. Use the Master buttons to select “Enable” or
“Disable.” When daylighting is disabled in a
scene, the GRAFIK Eye
®
QS control unit will
not respond to daylight sensors information
when that scene is active.
Press OK to save.
6. Exit programming mode.
Labels
Daylighting
Scene 1
Scene 1
Daylighting
Enable
Scene setup
Labels
Daylighting
Saved