LumaSMART
®
User Manual
DNP3 Protocol Testing
•
129
The relay entries start at Number 16, consist of 16 groups of 5 consecutive entries showing each of the Relay
Control Values. Reference
in Section 5.2.1 for more information. The entries for each group, in order,
are:
•
Configuration (Enable/Normally Energized/ Normally Deenergized)
•
Alarm Setpoint Temperature
•
Restore Setpoint Temperature
•
Logic (Or/Avg)
•
Temperature Channel Inputs for Relay
In the following example we will set the Control for Relay #6 as follows:
•
Normally Deenergized
•
Alarm Setpoint of 35 °C
•
Restore Setpoint of 25 °C
•
Or logic
•
Temperature Channels inputs 5, 6 and 7
To change a value
:
1.
Open the command
Analog Output Block
, the following window will appear:
Analog Output Block
2.
Set the
Target
to
Use Command Window target selection.
3.
Set the
Point Number
to the desired value to change (see Section 8.8
4.
Set the
Variation
to
Short
.
5.
Set the
Value
to the desired value.
6.
Press
Once
.