LumaSMART
®
User Manual
DNP3 Protocol Testing
•
127
To change a value:
1.
Open the command
Analog Output Block
. And a window will appear:
Analog Output Block
2.
Set the
Target
to
Use Command Window target selection.
3.
Set the
Point Number
to the desired value to change (see Section 8.8
4.
Set the
Variation
to
Long
.
5.
Set the
Value
to the desired value,
6.
Press
Once
.
After the following sequence:
1.
Point Number 4, Value 5, Once
2.
Point Number 5, Value 19, Once
3.
Point Number 6, Value -20, Once
4.
Point Number 7, Value 200, Once
The new values in the
Data Window
should reflect the changes as:
Data Window displaying changes