LumaSMART
®
User Manual
Modbus Protocol Testing
•
95
119
Configuration Relay 12
0 = Disabled
1 = Normally Deenergized
2 = Normally Energized
Int16
Rel
ay
1
2
120
Alarm Set Point for Relay 12
Int16
121
Restore Set Point for Relay 12
Int16
122
Channels Driving Relay 12
MSB = CH16 / LSB = CH1
Int16
Bit Mapped
123
Control Setting for Relay Number 12
2 = OR Logic
1 = AVG Logic
Int16
124
Configuration Relay 13
0 = Disabled
1 = Normally Deenergized
2 = Normally Energized
Int16
Rel
ay
1
3
125
Alarm Set Point for Relay 13
Int16
126
Restore Set Point for Relay 13
Int16
127
Channels Driving Relay 13
MSB = CH16 / LSB = CH1
Int16
Bit Mapped
128
Control Setting for Relay Number 13
2 = OR Logic
1 = AVG Logic
Int16
129
Configuration Relay 14
0 = Disabled
1 = Normally Deenergized
2 = Normally Energized
Int16
Rel
ay
1
4
130
Alarm Set Point for Relay 14
Int16
131
Restore Set Point for Relay 14
Int16
132
Channels Driving Relay 14
MSB = CH16 / LSB = CH1
Int16
Bit Mapped
133
Control Setting for Relay Number 14
2 = OR Logic
1 = AVG Logic
Int16