LumaSMART
®
User Manual
IEC 61850 Protocol Testing
•
105
Verify by reviewing the LumaSMART relay setup screen:
LumaSMART Relay Setup Screen
The resulting temperature calculation is used to
drive the relay, see ‘Ref Temp:’ in screen above. It
can also be viewed through the 61850 interface at
the location: R
4
CSWI
4
> RefTemp > instMag > f
Given the Ref Temp of 38+ degrees, the relay should
Energize. This can be verified on the LumaSMART display
and also through the 61850 interface as follows:
R
4
CSWI
4
> Pos > stVal is ‘on’ indicating energized.
By changing the entry R
4
CSWI
4
> RelCfg > ctlVal
to 2
which specifies
Normally Energized
the relay should flip its
state and indicate:
7.5
Report Control
1.
There are 5 types of reports available through the protocol interface.
To display a report, expand the tree
LumaSMARTQ
>
LLN0
>
Report
Control
.
2.
Right click on a column of one of the 5 available reports and select
Enable
Report Control
. This can be repeated for multiple report
types. As shown below, the icon
will indicate that the report is
enabled.
3.
On the top menu, select
Tools
, then
Data Monitor
. The right
portion of the screen will then display a window to access the
contents of the reports. Click on the sign to show the
Report