LumaSMART
®
User Manual
DNP3 Protocol Testing
•
134
12
Analog Output FOT 4
Minimum Current
Uint32
FOT #
4
13
Analog Output FOT 4
Maximum Current
Uint32
14
Analog Output FOT 4
Minimum Temperature
Int32
15
Analog Output FOT 4
Maximum Temperature
Int32
16
Relay Configuration for Relay 1
0 = Disabled
1 = Normally DeEnergized
2 = Normally Energized
Uint32
Rel
ay
#
1
17
Alarm Setpoint for Relay 1
Int32
18
Restore Setpoint for Relay 1
Int32
19
Logic for Relay 1
2 = OR … 1 = AVG ... 0=None
Uint32
20
Channel Temperature Inputs for Relay 1
Bit Mapped (Bit 15 = Channel 16 … Bit 0 = Channel 1)
Uint32
21
Relay Configuration for Relay 2
0 = Disabled
1 = Normally DeEnergized
2 = Normally Energized
Uint32
Rel
ay
#
2
22
Alarm Setpoint for Relay 2
Uint32
23
Restore Setpoint for Relay 2
Uint32
24
Logic for Relay 2
2 = OR … 1 = AVG ... 0=None
Uint32
25
Channel Temperature Inputs for Relay 2
Bit Mapped (Bit 15 = Channel 16 … Bit 0 = Channel 1)
Uint32
26
Relay Configuration for Relay 3
0 = Disabled
1 = Normally DeEnergized
2 = Normally Energized
Uint32
Rel
ay
#
3
27
Alarm Setpoint for Relay 3
Int32
28
Restore Setpoint for Relay 3
Int32
29
Logic for Relay 3
2 = OR … 1 = AVG ... 0=None
Uint32
30
Channel Temperature Inputs for Relay 3
Bit Mapped (Bit 15 = Channel 16 … Bit 0 = Channel 1)
Uint32
31
Relay Configuration for Relay 4
0 = Disabled
1 = Normally DeEnergized
2 = Normally Energized
Uint32
Rel
ay
#
4
32
Alarm Setpoint for Relay 4
Int32
33
Restore Setpoint for Relay 4
Int32
34
Logic for Relay 4
2 = OR … 1 = AVG ... 0=None
Uint32
35
Channel Temperature Inputs for Relay 4
Bit Mapped (Bit 15 = Channel 16 … Bit 0 = Channel 1)
Uint32