0x0036 SSC Error Register
In this memory register you will find information about possible errors
that have occurred when connecting the module to an external shift
register chain.
Modbus Register
0x0036
Value Range
0x00-0x05
Default Value
-
Number of bytes available
1
Permanently stored
No
Access
Read Only
Meaning
0
No Error
1
Centre tap is not receiving any data, line de-
fective
2
Data In is not receiving any data
3
Number of input registers is not as expected
4
Number of output registers is not as expec-
ted
5
General error, e.g. electrical faults
Also see about this
2
Data Broker [
}
20]