KUNBUS-COM EtherCAT
51 / 135
0x0002-0x0003 Current
module status
In these memory registers you will find information for the current
module status.
Bit 5 indicates whether there is an error in the configuration of the
SSC Master mode. It is only set, however, during the initialisation of
the module. If an error occurs during ongoing operation, this is not
displayed here.
Memory Register 0x0002 (bit 0-15) contains the Low Word, Memory
Register 0x0003 (bit 16-31) contains the High Word.
Modbus Register
0x0002-0x0003
Value Range
-
Initial value
-
Number of bytes available
4
Permanently stored
No
Access
Read Only
Meaning
Bit 0
Fieldbus Run State
1: The field bus is in cyclical data exchange
0: The cyclical data connection is interrup-
ted
Bit 1
(Only available in SSC mode)
SSC SSR Master Run State
1: The synchronous serial interface is in
SSC mode and is exchanging data cyclically
0: No cyclical data exchange takes place.
Bit 2
Synchronous Serial Mapping Configuration
Error State
1: Configuration error in the mapping of the
SCC interface.
0: Configuration is ok.
Bit 3
SDI Mapping Configuration Error
1: Configuration error in the mapping for the
SDI.
0: Configuration is ok.
Bit 4
Fieldbus Communication Mapping Configur-
ation Error
1: Configuration error in the mapping for the
FBS interface.
0: Configuration is ok.
Bit 5
Synchronous Serial Configuration Error
1: General configuration error of the SCC in-
terface
0: Configuration is ok.
Memory Register