KUNBUS-COM EtherCAT
72 / 135
0x0032 Script Enable
Register
In this register you have the option to activate or to deactivate the
execution of a script.
You will find information about creating a script in the "KUNBUS-
Scripter" documentation supplied.
Modbus Register
0x0032
Value Range
0x00 - 0xff
Default Value
0x00
Number of bytes available
1
Permanently stored
Yes
Access
Read/Write
Meaning
0
Deactivated
1
Activated
0x0033 Script Port Register
In this register you have the option to select the interface by which
the script should communicate.
NOTICE
Please note that activation of a script influences the individual port.
E.g.: If the CDI port is used by the script, the CDI menu can no longer be
used until you have deactivated the script.
If the CDI port is used by the script, you can only deactivate the script by
writing the value 0 in the memory register 0x0032. You must restart the
module to apply the deactivation.
Modbus Register
0x0033
Value Range
0x00-0x01
Default Value
0x01
Number of bytes available
1
Permanently stored
Yes
Access
Read/Write
Meaning
0
CDI Interface
1
SDI Interface
Memory Register