KUNBUS-COM EtherCAT
56 / 135
0x0012 Set bitrate for the CDI
In this memory register you have the option, to set the bitrate for the
CDI
The new settings are applied after a reset (Power Off/On or write
Memory Register 0x0001 with value 0x0003).
Modbus Register
0x0012
Value Range
0x01-0x07
Default Value
0x07
Number of bytes available
1
Permanently stored
Yes
Access
Read/Write
Meaning
0x01
2400 bit/s
0x02
4800 bit/s
0x03
9600 bit/s
0x04
19200 bit/s
0x05
38400 bit/s
0x06
57600 bit/s
0x07
115200 bit/s
NOTICE
Automatic bitrate detection with the CDI is not possible.
Ø
If the configuration that was entered is invalid, the corresponding
registers use the following settings in order not to block the interface by
incorrect data:
è
115200 bit/s, 8 databits, 1 stop bit, even parity
Memory Register