206
LP - Positioning Parameters
This parameter is used to turn on the One Floor Positioning Control functionality
or to learn the high speed and shor
t floor slowdown distances.
When set to Learn Slowdown, the slowdown for the selected speed (high
speed or short floor) will be measured on the next run. Afterwards, LP01 will
automatically be set for positioning turned on.
This parameter shows the minimum required slow down distance, based
on the adjusted profile (acceleration, jerks, high speed) to slow down from
contract speed.
This value is the actual distance the drive uses to calculate the actual
deceleration profile for High Speed runs.
This value is the actual distance the drive uses to calculate the actual
deceleration profile for short floor runs
LP01
Position Control
LP02
Minimum Slowdown
Distance
LP03
High Speed Slowdown
Distance
LP04
Short Floor Slowdown
Distance
Summary of Contents for COMBIVERT F5
Page 1: ...COMBIVERT F5 ELEVATOR DRIVE Reference Manual Version 3 34 0F5LUB K334...
Page 203: ...203 LP Positioning Parameters LS02 LS01 LP03 LS02 LS01 LP03...
Page 347: ...Notes...
Page 348: ......