US - Basic Setup Parameters
After entering the basic setup parameters (US02-US04 & US06) the system
configuration must be written to the drive. This procedure loads the drive with
the correct parameters depending on the motor type and sets the correct limits
and scalings.
Upon successful loading, US05 will display Configuration OK.
A user can also save/load OEM defaults and read/write to various memory
locations. These are the following options available in US05:
Settings:
NUM
Not Configured
0
Configuration OK
1
Write Configuration to Drive
2
Read Configuration from Drive
3
Write Configuration to Flash
4
Read Configuration to Flash
5
Create OEM Default
8
Restore OEM Defaults
9
Restore KEB Defaults
10
If the parameters US02 System Units, US03 Motor Type, or US04 Control Type
are changed, the configuration will need to be reloaded in US05 for changes
to take effect.
If the US03 Motor Type is changed, then a subsequent
Write Configuration
to Drive
will result in the defaulting of drive parameters.
This parameter sets the contract speed which serves as an upper speed limit
for normal operation.
In addition, an overspeed level is automatically set at 110% of this value.
US05
Load Configuration
US06
Contract Speed
i