
169
LS - Speed Profile Parameters
Intermediate Speed 2. This speed setting uses the One Floor Speed pr
ofile
settings LS30-35 and LS38 Correction Distance. Max. Value: US06 Contract
Speed
Intermediate Speed 3. This speed setting uses the Emergency Speed profile
settings LS40-45 and LS47 Correction Distance. Max. Value: US06 Contract
Speed
Intermediate Speed 3 uses the profile settings labeled as Emergency
Speed.
LS08 - 10: Special Function Speeds
To utilize these special function speeds, an input must be assigned in LI04-11.
Run speed when selected by an input programmed for Earthquake Speed is
activated before the start of the run. The High Speed, Intermediate Speed
1, Intermediate Speed 2, and Intermediate Speed 3 selections are limited to
this speed. This speed setting uses the High Speed profile settings LS20-25.
Max Value: 150 fpm
Active when an input programmed for Emergency Power Speed is activated
before the run. All speeds adjusted higher than this speed are limited to this
value. This setting uses the High Speed profile settings LS20-25.
Max. Value: US06 Contract Speed
Run speed when selected by an input programmed for UPS Operation is active
before the start of the run. All speeds are limited to this value. This setting uses
the High Speed profile settings LS20-25. When using an externally generated
speed profile from analog or serial speed control modes, the acceleration and
deceleration rates are determined by the controller.
Max. Value: 50 fpm
LS07
Intermediate Speed 3
LS06
Intermediate Speed 2
i
LS08
Earthquake Speed
LS09
Emergency Generator
Speed
LS10
Battery Operation
Speed
Summary of Contents for COMBIVERT F5
Page 1: ...COMBIVERT F5 ELEVATOR DRIVE Reference Manual Version 3 34 0F5LUB K334...
Page 203: ...203 LP Positioning Parameters LS02 LS01 LP03 LS02 LS01 LP03...
Page 347: ...Notes...
Page 348: ......