5. Quick Setup
- 87 -
START
Para.
Parameter name
Default
Commission
Before power on
Install and wire the drive
Install and wire the drive as explained in chapters 1 to 3.
Check wirings
-
of power supply and AC drive
outputs
Restore parameters
FP-01
Parameter initialization
0
0: No operation
1: Restore default settings except motor parameters
2: Clear records including errors
4: Back up parameters
501: Restore user’s backup parameters
NOTE: It is recommended to "Restore default settings" prior
to commissioning the AC drive.
Set motor parameters
Motor Nameplate
F1-01
Rated motor power
model
dependent
1.5
Unit: kW
F1-02
Rated motor voltage
model
dependent
380
Unit: V
F1-03
Rated motor current
model
dependent
3.4
Unit: A
F1-04
Rated motor frequency
model
dependent
50
Unit: Hz
F1-05
Rated motor speed
model
dependent
2800
Unit: rpm.
CONTINUE