6. Description of Parameters
Function Code
Parameter Name
Setting Range
Default
F5-09
Max. FMP output frequency
0.01 to 100.00 kHz
50.00 kHz
This function parameter sets maximum pulse output frequency when FM terminal is used for
pulse output.
Function Code
Parameter Name
Setting Range
Default
F5-10
AO1 zero offset coefficient
-100.0% to 100.0%
0.0%
F5-11
AO1 gain
-10.00 to 10.00
1.00
F5-12
AO2 zero offset coefficient
-100.0% to 100.0%
0.00%
F5-13
AO2 gain
-10.00 to 10.00
1.00
These four function parameters generally correct zero offset of analog output and output
amplitude error. They can also define required AO curve.
Zero offset coefficient 100% of AO1 and AO2 corresponds to 10 V or 20 mA. You can calculate
the gain and the zero offset coefficient from the following formulas:
K
(Y1
–
Y2) x Xmax
=
(X1
–
X2) x Ymax
(X1 xY2
–
X2 x Y1)
b =
(X1
–
X2) x Ymax
In the formulas:
●
"b" represents zero offset.
●
"k" represents gain.
●
"X" represents output frequency.
●
"Y" represents actual output of the AO.
●
" Xmax " represents max. output frequency (determined by F0-10).
●
"Ymax" represents max. output 10 V or 20 mA.
For example, AO is used for output of frequency reference. To implement output of 8 V (Y1) at 0
Hz (x1) and output of 4 V (Y2) at 40 Hz (X2) according to the formulas, you can obtain gain and
zero offset coefficient as follows:
K =
(8
–
4) x 50
(0
–
40) x 10
(0 x 4 - 40 x 8)
=
–
0.5
b =
(0 - 40) x 10
= 80%
Then you can set F5-11 to -0.5 and set F5-10 to 80%.
AO output signal type and corresponding max. value are as follows:
AO1 output signal
Corresponding Max. Output (Ymax)
Voltage
10 V
Current
20 mA
6