2. Mechanical Installation
- 34 -
2
Cabinet ventilation
top cover
Wind screen
Transformer (from
380 V to 220 V)
Ventilation
airflow of
GT600
Breaker
Cabinet
Front door
2200 mm
Contactor
GT600
(450 kW)
Cabinet input
copper bar
Front door
air inlet
AC input reactor
100mm
Cabinet base
Grounding
Output
terminal of GT600
copper bar
●
The cabinet dimension is 2200 x 800 x 600 mm. The height 2200 mm includes
the 200 mm cabinet ventilation top cover but does not include the 100 mm
cabinet base.
●
After push-in, remove the baffle on the top of the drive, preventing occurrence of
overcurrent because ventilation air cannot flow out.
There are three steps of installing the AC drive in cabinet.
Step 1: Get acquainted with cabinet layout.
Figure 2-14 Recommended cabinet layout of GT600-4T350G to GT600-4T450
Note