Appendix A Standards Compliance
12
- 322 -
C
F
E
■
dv/dt Reactor Installation
Connect a dv/dt reactor on the output side to reduce large dv/dt, protecting the motor
winding from insulation breakdown, lowering motor temperature and extending the motor
service life and meanwhile reduce interference on surrounding devices.
●
Selection of the dv/dt reactor (Schaffner)
AC Drive Model
dv/dt Reactor
Model
Rated
Current at
40°C (A)
Rated Motor
Power (kW)
Rated
Inducance
(mH)
Power
Consumption
(W)
I/O Terminal
Selection
Total
(kg)
GT600-
4T18.5GB
RWK 305-45-KL
45
18.5
0.131
60
KL
-
-
6.1
GT600-4T22GB
RWK 305-45-KL
45
22
0.131
60
KL
-
-
6.1
GT600-4T30GB
RWK 305-60-KL
60
30
0.098
65
KL
-
-
6.1
GT600-4T37GB
RWK 305-72-KL
72
37
0.082
70
KL
-
-
6.1
GT600-4T45GB
RWK 305-90-KL
90
45
0.065
75
KL
-
-
7.4
GT600-4T55GB
RWK 305-110-KL
110
55
0.053
90
KL
-
-
8.2
GT600-4T75GB
RWK 305-156-KS
156
75
0.038
120
-
K
S
-
10.7
GT600-4T90G
RWK 305-182-KS
182
90
0.032
140
-
K
S
-
16
GT600-4T110G
RWK 305-230-KS
230
110
0.026
180
-
K
S
-
22
GT600-4T132G
RWK 305-280-KS
280
132
0.021
220
-
K
S
-
29
GT600-4T160G
RWK 305-330-KS
330
160
0.018
240
-
K
S
-
32
GT600-4T200G
RWK 305-400-S
400
200
0.015
330
-
-
S
34
GT600-4T220G
RWK 305-500-S
500
220
0.012
340
-
-
S
35
GT600-4T250G
RWK 305-500-S
500
250
0.012
340
-
-
S
35
GT600-4T280G
RWK 305-600-S
600
280
0.01
380
-
-
S
37
GT600-4T315G
RWK 305-600-S
600
315
0.01
380
-
-
S
37
GT600-4T355G
RWK 305-680-S
680
355
0.009
410
-
-
S
38
GT600-4T400G
RWK 305-790-S
790
400
0.007
590
-
-
S
43
GT600-4T450G
RWK 305-910-S
910
450
0.006
740
-
-
S
49
●
Mounting Dimensions (Unit: mm)
4-45A
G
A
B
D
Summary of Contents for GT600-4T132G
Page 1: ...GT600 AC Drive...
Page 5: ......
Page 86: ...5 Quick Setup 5 1 Get Familiar With Operating Panel 86 5 2 Setup Flowchart 87...
Page 87: ......
Page 100: ...5 Quick Setup 98 5...
Page 280: ...8 Peripherals and Options 278 8...
Page 306: ...12 303 11...
Page 362: ......