6. Description of Parameters
- 100 -
RUN
RES
Chapter 6 Description of Parameters
6.1 Start/Stop Command Source
Three control methods are available:
●
Operating panel (keypad & display)
●
Terminal I/O control
●
Serial communication
You can select the required control mode in function parameter F0-02.
Function Code
Parameter Name
Setting Range
Default
F0-02
Command source selection
0: Operating panel (keypad & display) (LED off)
1: Terminal I/O control (LED on)
2: Serial comms. (LED flashing)
0
●
F0-02 = 0: Operating panel (keypad & display) (The LOCAL/REMOT indicator is off.)
The RUN commands are given by pressing keys
and
STOP
on the operating panel.
– Press
– Press
to start the AC Drive.
to stop the AC Drive.
For details on operating panel, refer to
.
●
F0-02 = 1: Terminal I/O control (The LOCAL/REMOT indicator is on.)
The terminal I/O control mode applies to installations where the Start and Stop signals come from:
– A DIP switch or electromagnetic button, or
– A dry contact signal source
Commands are given by using multi-functional input terminals with functions such as FWD, REV,
JOGF and JOGR.
For details on terminal I/O control, see
.
●
F0-02 = 2: Serial comms (The LOCAL/REMOT indicator is flashing.)
The available serial communication options are Modbus, PROFIBUS-DP, CANlink, CANopen.
For details on serial communication, see
.
6
RUN
STOP
RES