3. Electrical Installation
- 57 -
Screen/shield
Cable support
bracket (option)
Use heatshrink tube or
insulation tape to terminate
the screen/shield.
Grounding clamp
for screen/shield
Main circuit cables
■
Braking Resistor
CAUTION
■
AC Drive Outputs U, V, W to Motor
3
●
Fire risk! Fit overtemperature sensors or thermal overload relay to
the braking resistor, and use double insulated cables for the dynamic
brake circuit to the brake resistors.
●
Braking resistor terminals (+) and PB are only for the drive units up to
75 kW that are fitted with an internal braking unit.
●
To avoid risk of equipment damage, use a cable not exceeding 5 m to
connect an external braking resistor.
●
To avoid risk of ignition due to overheating of the braking resistor, do
not place anything combustible around the braking resistor.
●
Set F6-15 (Braking use ratio) and F9-08 (Braking unit action initial
voltage) correctly according to load after connecting braking resistor to
the drive of up to 75 kW that is fitted with an internal braking unit.