Appendix A Standards Compliance
12
- 319 -
■
AC Output Reactor Installation
Whether to install an AC output reactor on power output side is dependent on actual
situation. Cable connecting AC drive and motor should not be too long; capacitance
enlarges when an over-long cable is used and thus high-harmonics current may be easily
generated.
When an output reactor used, cable length can be increased to the value in below table.
AC Drive Power (kW)
Rated Voltage (V)
Cable Length Limit (m)
4
200 to 500
50
5.5
200 to 500
70
7.5
200 to 500
100
11
200 to 500
110
15
200 to 500
125
18.5
200 to 500
135
22
200 to 500
150
≥ 30
280 to 690
150
●
AC Output Reactor Model
Recommended AC output reactor manufacturer and models are listed in the following
table.
AC Drive Model
AC Output Reactor Model (K&R)
GT600-4T18.5GB
MD-OCL-50-0.14-4T-1%
GT600-4T22GB
MD-OCL-60-0.12-4T-1%
GT600-4T30GB
MD-OCL-80-0.087-4T-1%
GT600-4T37GB
MD-OCL-90-0.078-4T-1%
GT600-4T45GB
MD-OCL-120-0.058-4T-1%
GT600-4T55GB
MD-OCL-150-0.047-4T-1%
GT600-4T75GB
MD-OCL-200-0.035-4T-1%
GT600-4T90G
MD-OCL-250-0.028-4T-1%
GT600-4T110G
MD-OCL-250-0.028-4T-1%
GT600-4T132G
MD-OCL-330-0.021-4T-1%
GT600-4T160G
MD-OCL-330-0.021-4T-1%
●
Designation rules
MD-OCL
50
0.14
4T
1%
Mark
0.14
Inductance
0.14 mH
50 A
50
Rated Current
Mark
Inovance AC Output
Reactor
1%
1%
Voltage Drop Percentage
Mark
380 V
4T
Rated Voltage