Appendix A Standards Compliance
12
- 307 -
■
Installing Fuse on the Input Side
To prevent accidents caused by short circuit, install fuse on the input side and the fuse
must comply with the UL standard.
Select the fuse according to the following figure.
GT600 Model
FWH Series Fuse
Manufacturer: Bussmann
Rated Current (A)
Model
GT600-4T18.5GB
80
FWH-80B
GT600-4T22GB
100
FWH-100B
GT600-4T30GB
100
FWH-100B
GT600-4T37GB
125
FWH-125B
GT600-4T45GB
150
FWH-150B
GT600-4T55GB
200
FWH-200B
GT600-4T75GB
250
FWH-250B
GT600-4T90G
275
FWH-275B
GT600-4T110G
325
FWH-325B
GT600-4T132G
400
FWH-400B
GT600-4T160G
500
FWH-500B
GT600-4T200G
600
FWH-600B
GT600-4T220G
700
FWH-700B
GT600-4T250G
800
FWH-800B
GT600-4T280G
800
FWH-800B
GT600-4T315G
1000
170M5016
GT600-4T355G
1000
170M5016
GT600-4T400G
1400
170M6017
GT600-4T450G
1400
170M6017
■
Preventing Entry of Foreign Objects
The drive units must be installed in a fireproof cabinet with doors that provide effective
electrical and mechanical protection. The installation must conform to local and regional
laws and regulations, and to relevant IEC requirements.
■
Grounding
If using an AC drive of the 400 V class, connect the neutral point of the drive power supply
to ground.