5. Quick Setup
- 96 -
CONTINUE
Para.
Parameter name
Default
Commission
if it is VF control
Set VF parameters
F3-00
V/F curve selection
0
0: Linear V/F
1: Multi-point V/F
2: Square V/F
3: 1.2-power V/F
4: 1.4-power V/F
6: 1.6-power V/F
8: 1.8-power V/F
9: Reserved
10: V/F complete separation
11: V/F half separation
SETTING RANGE: 0 to 11;
F3-01
Torque boost
0.0
0.0 to 30.0 %;
NOTE: if it is 0, then auto torque boost is activated, and it
is recommended to use auto torque boost.
F3-02
Frequency limit of torque boost
50.00
0.00 Hz to maximum output frequency
F3-03
Multi-point V/F frequency 1
0.00
0.00 Hz to F3-05
F3-04
Multi-point V/F voltage 1
0.0
0.0 to 100.0 V
F3-05
Multi-point V/F frequency 2
0.00
F3-03 to F3-07, Hz
F3-06
Multi-point V/F voltage 2
0.0
0.0 to 100.0 V
F3-07
Multi-point V/F frequency 3
0.00
F3-05 to rated motor frequency F1-04, Hz
F3-08
Multi-point V/F voltage 3
0.0
0.0 to 100.0 V
Trial RUN
Use operating panel, or digital input terminal, or serial
communication control, to start AC Drive, check if the
running performance satisfies your application. If yes, then
go forward to next step, if NO, then go back to check.
CONTINUE
Para.
Parameter name
Default
Commission
5
Summary of Contents for GT600-4T132G
Page 1: ...GT600 AC Drive...
Page 5: ......
Page 86: ...5 Quick Setup 5 1 Get Familiar With Operating Panel 86 5 2 Setup Flowchart 87...
Page 87: ......
Page 100: ...5 Quick Setup 98 5...
Page 280: ...8 Peripherals and Options 278 8...
Page 306: ...12 303 11...