8 Error messages and alarms
UCEsat 1 protec-
tive switch-off
Error in the power output stage. To prevent
destruction of the device, a firing pulse in-
hibit is triggered permanently.
The device must be returned to JUMO
for repair.
UCEsat 2 protec-
tive switch-off
Fault current too
high
The error current monitoring using external
current sensors has detected that the error
current limit value has been exceeded.
Rectify the cause of the error cur-
rent.
Failure fan 1, 2
Fan 1/2 does not reach the necessary
speed.
Check fan for freedom of movement
(dirt).
[xxx] Invalid
configuration
The value range of a configured parameter
has not been complied with. A firing pulse
inhibit has therefore been triggered for
some parameters.
The square brackets contain an ID for the
parameter concerned:
002
Mains frequency
003
Language wizard active
004
Language
005
Temperature unit
006
Display contrast
007
Switch-off display lighting
008
Apply default settings
010
Subordinate control loop
011
Soft start
012
Soft start duration
013
Voltage supply U-N(V)
014
Customer-spec. voltage
015
Max. load voltage
016
Max. load current
017
Max. power
018
Resistance limitation
019
Max. load resistance
021
Current measuring range
022
Current range start
023
Current range end
024
Voltage measuring range
025
Voltage range, start
026
Voltage range, end
027
Setpoint value config.
028
Setpoint specification
029
Input in the event of an error
030
Value in the event of an error
031
Base load
Ext. current sensor 2:
034
Measurand
035
Sensor outp. signal
036
Outp. meas. range start
037
Outp. meas. range end
038
Sensor input measuring range
039
Input meas. range start
040
Input meas. range end
041
Limit value error current
Re-configure the parameter con-
cerned, complying with its value
range.
Error message
Cause
Remedy
Summary of Contents for 709051
Page 8: ...8 V1 00 EN 00741192 2021 03 30 IPC 300 Contents...
Page 26: ...2 Mounting 26 V1 00 EN 00741192 2021 03 30 IPC 300...
Page 48: ...4 Operation 48 V1 00 EN 00741192 2021 03 30 IPC 300...
Page 62: ...5 Configuration 62 V1 00 EN 00741192 2021 03 30 IPC 300...
Page 76: ...6 Special device functions 76 V1 00 EN 00741192 2021 03 30 IPC 300...
Page 84: ...8 Error messages and alarms 84 V1 00 EN 00741192 2021 03 30 IPC 300...
Page 90: ...10 Technical data 90 V1 00 EN 00741192 2021 03 30 IPC 300...
Page 91: ...V1 00 EN 00741192 2021 03 30 IPC 300 91 11 Certificate 11 1 China RoHS...