V1.00/EN/00741192/2021-03-30 [IPC 300]
67
6 Special device functions
with time due to aging.
When the power controller is disconnected from the mains voltage, the Teach-
In values detected last are deleted and recalculated once the mains voltage
supply has returned.
6.3 Manual mode
In this case, the setpoint value can be manually preset from 0 to 100 % with-
out the need for external wiring via the analog input.
6.3.1 Setpoint specification in manual mode
Starting
Manual mode, as set per default, can be accessed without entering a code.
h
Press the
key once (selection menu)
h
Press the
key again (manual mode)
h
Use the
or
key to increase or decrease the setpoint value
The changes become effective immediately at the load output and are indicat-
ed on the display.
6.3.2 Configuring Teach-In (prerequisite for Teach-In in manual mode)
The Teach-In function records the current/voltage ratio of a load in the OK
state.
Configuring
"manual"
Teach-In
The power controller is in the "Measured value overview" level.
h
Press the
key
Config. level
r
Monitoring
r
Load monitoring
r
Undercurrent or overcurrent
r
Teach-in type load monit.
r
Set to
"manual"
h
Press the
key
II
h
Press the
key twice
If Teach-In is being performed for the first time, the message "Teach-In miss-
ing" appears in the bottom line of the display.
Load voltage
Load current
Setpoint value
The setpoint value for manual mode is not saved in the event of a power failure!
Summary of Contents for 709051
Page 8: ...8 V1 00 EN 00741192 2021 03 30 IPC 300 Contents...
Page 26: ...2 Mounting 26 V1 00 EN 00741192 2021 03 30 IPC 300...
Page 48: ...4 Operation 48 V1 00 EN 00741192 2021 03 30 IPC 300...
Page 62: ...5 Configuration 62 V1 00 EN 00741192 2021 03 30 IPC 300...
Page 76: ...6 Special device functions 76 V1 00 EN 00741192 2021 03 30 IPC 300...
Page 84: ...8 Error messages and alarms 84 V1 00 EN 00741192 2021 03 30 IPC 300...
Page 90: ...10 Technical data 90 V1 00 EN 00741192 2021 03 30 IPC 300...
Page 91: ...V1 00 EN 00741192 2021 03 30 IPC 300 91 11 Certificate 11 1 China RoHS...