V1.00/EN/00741192/2021-03-30 [IPC 300]
43
4 Operation
Meaning of the
symbols in the
info line
4.1.3 Meaning of the displayed measured values
Input signal
Subordinate
control loop
Operating mode
load output
Voltage
U
2
Firing pulse inhibit
Current
I
2
Soft start
Interface
U
Current output level
I
P
Measured value
Meaning
Unit
Load voltage
Effective value of the measured load voltage
(Measured between the D and 1D terminals)
V
Load current
Effective value of the measured load current
A
Power
Measured effective power Note:
Four-digit display in watts; values above 9999 W are shown in kW.
W
or
kW
Load resistance
Calculated resistance value of the load
Ω
Intermediate
circuit volt.
Effective value of the measured DC intermediate circuit voltage.
V
External current in-
put 1 to 3
Depending on the configuration
Digital input 1, 2
Display of logic level
0 or 1
Inhibit input
Display of logic level
0 or 1
Device tempera-
ture
Currently measured temperature inside the power controller
°C
or
°F
Voltage
input
Measured value for the power controller's voltage input
(Measured between terminals 3 and 4 on X2_1)
V
Current input
Measured value for the power controller's current input
(Measured between terminals 1 and 2 on X2_1)
mA
Input
setpoint value
Externally specified setpoint value for the subordinate control loop
%
Effective
setpoint value
The effective setpoint value may deviate from the input setpoint value due
to internal functions, such as the soft start or base load.
%
Output level, con-
troller
Percentage controller output level of the subordinate control loop
%
Output level, PWM
Percentage controller output level of the PWM (pulse width modulation)
%
Summary of Contents for 709051
Page 8: ...8 V1 00 EN 00741192 2021 03 30 IPC 300 Contents...
Page 26: ...2 Mounting 26 V1 00 EN 00741192 2021 03 30 IPC 300...
Page 48: ...4 Operation 48 V1 00 EN 00741192 2021 03 30 IPC 300...
Page 62: ...5 Configuration 62 V1 00 EN 00741192 2021 03 30 IPC 300...
Page 76: ...6 Special device functions 76 V1 00 EN 00741192 2021 03 30 IPC 300...
Page 84: ...8 Error messages and alarms 84 V1 00 EN 00741192 2021 03 30 IPC 300...
Page 90: ...10 Technical data 90 V1 00 EN 00741192 2021 03 30 IPC 300...
Page 91: ...V1 00 EN 00741192 2021 03 30 IPC 300 91 11 Certificate 11 1 China RoHS...