21
2 Mounting
2.3 Environmental influences
Incorrect use
The device is not suitable for installation in potentially explosive areas.
Mounting site
The mounting site should be free from vibration, dust, and corrosive media.
In accordance with the conditions specified in VDE 0660-514, the device is
finger safe (IP20) and must be installed in a control cabinet.
Climatic
conditions
- Relative humidity : 5 to 85 %, no condensation (3K3 according to EN
60721)
- Max. air inlet temperature 35 °C
- Ambient temperature range: 5 to 40 °C (3K3 according to EN 60721)
- Storage temperature range: -10 to 70 °C
Power loss
Power loss occurs in the form of waste heat at the heat sink of the IPC 300, at
the mains filter, and choke, and has to be dissipated at the mounting site (e.g.
in the control cabinet) in accordance with the climatic conditions.
IPC300 type
Voltage sup-
ply
for power
section
Maximum power
loss P
Loss max.
Power loss P
Loss
of the applica-
tion
709051/X-XX-070...
400 V
770 W
230 V
450 W
115 V
280 W
709051/X-XX-100...
400 V
1100 W
230 V
640 W
115 V
400 W
709051/X-XX-200...
400 V
1740 W
230 V
1400 W
115 V
960 W
1
1
-PTT
-PTTNBY
*
"QQM
*
SBUFE
*
-PBEDVSSFOUPOOBNFQMBUF
SBUFE
*
-PBEDVSSFOUPGUIFBQQMJLBUJPO
"QQM
1
1PXFSMPTT UIBUBSJTFTPO
-PTT
'JMUFS$IPLFBOEJOTJEF*1$
Summary of Contents for 709051
Page 8: ...8 V1 00 EN 00741192 2021 03 30 IPC 300 Contents...
Page 26: ...2 Mounting 26 V1 00 EN 00741192 2021 03 30 IPC 300...
Page 48: ...4 Operation 48 V1 00 EN 00741192 2021 03 30 IPC 300...
Page 62: ...5 Configuration 62 V1 00 EN 00741192 2021 03 30 IPC 300...
Page 76: ...6 Special device functions 76 V1 00 EN 00741192 2021 03 30 IPC 300...
Page 84: ...8 Error messages and alarms 84 V1 00 EN 00741192 2021 03 30 IPC 300...
Page 90: ...10 Technical data 90 V1 00 EN 00741192 2021 03 30 IPC 300...
Page 91: ...V1 00 EN 00741192 2021 03 30 IPC 300 91 11 Certificate 11 1 China RoHS...