V1.00/EN/00741192/2021-03-30 [IPC 300]
53
5 Configuration
1.
Inverting analog inputs:
If, for example, the current measuring range start is set to 20 mA and the current measuring range end
is set to 0 mA, the power controller is switched off at 20 mA and switched on at 0 mA.
5.1.4
Setpoint configuration
This setting determines which input specifies the setpoint value, how high the base
load is, and which replacement value should be applied in the event of malfunction.
Voltage measuring
range, start
0 to 10 V
Note: This parameter only appears if "Customer specific" is
set for the voltage measuring range (see above)!
Voltage measuring
range, end
0 to 10 V
Note: This parameter only appears if "Customer specific" is
set for the voltage measuring range (see above)!
Value / settings
Description
k
/ bold = default setting
Value / settings
Description
Setpoint specifica-
tion
Current input
This setting specifies where the setpoint value for the power
output comes from.
Voltage input
Via interface
Input in the event
of an error
Current, voltage, and interface input are monitored for errors
(wire breaks or bus errors). This setting specifies which replace-
ment value the power controller should use if the setpoint spec-
ification is incorrect.
Last value
Voltage input
If, for example, an error (e.g. wire break) now occurs at the cur-
rent input that is selected for the default setpoint specification,
the power controller uses the value at the voltage input.
Current input
Value, adjustable
This means that the "Value in the event of an error" is used.
Value in the event
of an error
000.0
If "Value, adjustable" is configured as the error value, this value
is used in the event of a malfunction.
Summary of Contents for 709051
Page 8: ...8 V1 00 EN 00741192 2021 03 30 IPC 300 Contents...
Page 26: ...2 Mounting 26 V1 00 EN 00741192 2021 03 30 IPC 300...
Page 48: ...4 Operation 48 V1 00 EN 00741192 2021 03 30 IPC 300...
Page 62: ...5 Configuration 62 V1 00 EN 00741192 2021 03 30 IPC 300...
Page 76: ...6 Special device functions 76 V1 00 EN 00741192 2021 03 30 IPC 300...
Page 84: ...8 Error messages and alarms 84 V1 00 EN 00741192 2021 03 30 IPC 300...
Page 90: ...10 Technical data 90 V1 00 EN 00741192 2021 03 30 IPC 300...
Page 91: ...V1 00 EN 00741192 2021 03 30 IPC 300 91 11 Certificate 11 1 China RoHS...