
4 Operation
46
V1.00/EN/00741192/2021-03-30 [IPC 300]
4.2.3 Setpoint value configuration
4.2.4 Monitoring
The value to be monitored can be adjusted.
v
Chapter 5.1.5 "Ext. current sensor 2 and 3"
The load voltage was used in this example.
Value range
Description
000.00
If "Value, adjustable" is configured as the error value, this
value is used in the event of a malfunction as the setpoint
value at the set analog input.
Current load volt-
age
0 to U
Max.
of the load voltage
(U
Max.
= voltage supply to
the power section
-20 V)
0 to P
Max.
of the power
(
P
Max.
=
U
Max.
×
I
Nom.
)
0 to I
Nom.
of the max. load current
0 to 100 %
of the output level
Note:
The base load setting depends on the subordinate control
loop:
- For voltage: 0 to 100 %
U
Max.
(e.g. 0 V)
- For current: 0 to 100 % I
Nom.
(e.g. 0 A)
- For power: 0 to 100 % P
Max.
(e.g. 0 W)
- None: 0 to 100 % of output level (e.g. 0 %)
Example:
k
/ bold = default setting
Control signal
P
Base load: 680 W
Maximum
Output level: 3680 W
0 mA
20 mA
3000W
0...20mA
Ⳏ
Base load
Value range
Description
Current measured value
0 to 9999.9
Absolute minimum limit values for load voltage, load current, pow-
er in W and kW, load resistance, DC intermediate circuit voltage, or
device temperature can be monitored.
v
Chapter 5.1.5 "Ext. current sensor 2 and 3"
Example:
If the voltage falls below 20 V, an alarm is issued.
Current measured value
0 to 9999.9
Absolute max. limit values for load voltage, load current, power in
W and kW, load resistance, DC intermediate circuit voltage,
or de-
vice temperature can be monitored.
v
Chapter 5.1.5 "Ext. current sensor 2 and 3"
Example:
If the voltage exceeds 100 V, an alarm is issued.
Summary of Contents for 709051
Page 8: ...8 V1 00 EN 00741192 2021 03 30 IPC 300 Contents...
Page 26: ...2 Mounting 26 V1 00 EN 00741192 2021 03 30 IPC 300...
Page 48: ...4 Operation 48 V1 00 EN 00741192 2021 03 30 IPC 300...
Page 62: ...5 Configuration 62 V1 00 EN 00741192 2021 03 30 IPC 300...
Page 76: ...6 Special device functions 76 V1 00 EN 00741192 2021 03 30 IPC 300...
Page 84: ...8 Error messages and alarms 84 V1 00 EN 00741192 2021 03 30 IPC 300...
Page 90: ...10 Technical data 90 V1 00 EN 00741192 2021 03 30 IPC 300...
Page 91: ...V1 00 EN 00741192 2021 03 30 IPC 300 91 11 Certificate 11 1 China RoHS...