6 Special device functions
68
V1.00/EN/00741192/2021-03-30 [IPC 300]
6.3.3 Performing Teach-In in manual mode
The power controller is in the "Measured value overview" level.
h
Press the
key twice to return to manual mode.
If Teach-In is being performed for the first time, the message "Teach-In miss-
ing" now appears in the bottom line of the display.
h
Press the
key and the following message appears:
h
Press the
key to apply the current load state as the OK state.
Reason
For the Teach-In process, at least 5% of the set max. load current must flow
so that the correct resistance values for the Teach-In process can be calculat-
ed.
A change in the load (load fault) will be evaluated by the device on the basis of
this state.
Repeating
Teach-In
Teach-In can be repeated any number of times in manual mode.
h
Press the
key and the following message appears:
NOTE:
If the load parameters:
- Max. load voltage
- Max. load current
- Max. power
are set too far or deviate too much from the actual working point of the load,
this may mean the Teach-In is not applied. The message "Teach-In missing" is
then still shown on the display.
Summary of Contents for 709051
Page 8: ...8 V1 00 EN 00741192 2021 03 30 IPC 300 Contents...
Page 26: ...2 Mounting 26 V1 00 EN 00741192 2021 03 30 IPC 300...
Page 48: ...4 Operation 48 V1 00 EN 00741192 2021 03 30 IPC 300...
Page 62: ...5 Configuration 62 V1 00 EN 00741192 2021 03 30 IPC 300...
Page 76: ...6 Special device functions 76 V1 00 EN 00741192 2021 03 30 IPC 300...
Page 84: ...8 Error messages and alarms 84 V1 00 EN 00741192 2021 03 30 IPC 300...
Page 90: ...10 Technical data 90 V1 00 EN 00741192 2021 03 30 IPC 300...
Page 91: ...V1 00 EN 00741192 2021 03 30 IPC 300 91 11 Certificate 11 1 China RoHS...